| S.No. | Scheme ID | Scheme Name | OHT Code | Non-Compliance | Compliance(Current Status) | Description
|
||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Major Honey Comb | Alignment | Cube Test | Exposure | Deviation | Tank Observation | Other | SBC Issue | Demolish Partially | Demolish Fully | Under Examination | Serious Observation | Water Body | Compliance Major Honey Comb | Compliance Alignment | Compliance Cube Test | Compliance Exposure | Compliance Deviation | Compliance Tank | Compliance Other | Compliance SBC Issue | Compliance Demolish Partially | Compliance Demolish Fully | Compliance Under Examination | Compliance Serious Observation | Compliance Water Body | |||||
| 1 | 8360726 | RATANPUR W/S SCHEME | P2FBD128 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 2 | 20076404 | Faridpur Saidvada w/s scheme | P2FBD108 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 3 | 8359281 | BARARIKH W/S SCHEME | P2FBD03 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 4 | 20092642 | Husainpur Masmuley Dariyapur MVS | P2FBD36 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 5 | 8359193 | CHUNUPUR GADHIYA W/S SCHEME | P2FBD119 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 6 | 20074326 | MAHMOODPUR SINAURA SVS | P2FBD204 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 7 | 20092496 | Narayanpur MVS | P2FBD194 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 8 | 20092588 | Patti Madari MVS | P2FBD193 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 9 | 20038805 | Nyamtpur Dilavali Multi V w/s scheme | P2FBD190 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN NALA | |||||||||||||
| 10 | 20097767 | Samauddinpur SVS | P2FBD207 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 11 | 8388560 | RATHAURA NAGLA NIV W/S SCHEME | P2FBD130 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 12 | 20074362 | NAHRAIYA SVS | P2FBD146 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 13 | 20013921 | Rasulpur Urf Bharatpur | P2FBD15 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 14 | 8362323 | RAJARAMPUR MEI W/S SCHEME | P2FBD16 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 15 | 8359353 | PUTHARI W/S SCHEME | P2FBD08 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 16 | 20018373 | Jiyouna W/S Scheme | P2FBD54 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 17 | 20074331 | PAHARPUR BAIRGAR SVS | P2FBD96 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 18 | 20023534 | Kuiyadhir W/S Scheme | P2FBD89 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 19 | 20097758 | Mahrupur Khar MVS | P2FBD157 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN NALA | |||||||||||||
| 20 | 20074334 | PURAURI SVS | P2FBD202 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 21 | 20074360 | BAHBALPUR SVS | P2FBD151 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 22 | 20023305 | Bankati W/S Scheme | P2FBD28 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 23 | 8359381 | PANJU KHIRIYA W/S SCHEME | P2FBD126 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 24 | 20092323 | Mahmudpur Achla & Kandhrapur MVS | P2FBD148 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 25 | 20022072 | Jaitpur W/S Scheme | P2FBD112 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT WITHIN 100 MTR RADIUS IN POND | |||||||||||||
| 26 | 20019514 | Patti Khurd | P2FBD22 | No | No | No | No | No | No | No | No | No | No | No | No | No | OHT Column not found in center line. | |||||||||||||
| 27 | 8359330 | MUNDGAON W/S SCHEME | P2FBD06 | No | No | No | No | No | No | No | No | No | No | No | No | No | BBS Not provided before casting 2nd brace beam. | |||||||||||||
| 28 | 8359185 | ISHEPUR W/S SCHEME | P2FBD117 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Gap Between slab & sheet, Improper centering of ring beam. | |||||||||||||
| 29 | 8359220 | NAGARIYA W/S SCHEME | P2FBD123 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Leakage in bottom of tank & installed corrugated sheet. | |||||||||||||
| 30 | 20020879 | Bhartamau W/S Scheme | P2FBD136 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Tank not placed centre of ring beam, Improper levelling. | |||||||||||||
| 31 | 20038913 | Katrauli Patti w/s scheme | P2FBD143 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Nut bolt rusted, Tank not placed centre of ring beam. | |||||||||||||
| 32 | 20093607 | NAULI SVS | P2FBD86 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Tank not placed centre of ring beam and hold down bracket not vertically. | |||||||||||||
| 33 | 20019511 | Ramapur Dabir W/S Scheme | P2FBD56 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Tank not placed center of ring beam hold down bracket not vertically. | |||||||||||||
| 34 | 8359178 | RANUKHERA W/S SCHEME | P2FBD115 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Rusted nut bolt & gap between slab and sheet. | |||||||||||||
| 35 | 20023686 | Santoshpur W/S Scheme | P2FBD90 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Z Truss assembly roof arrangement sheet used in 2.6 mm instead of minimum required 3mm & Tank not vertically. | |||||||||||||
| 36 | 20023193 | BEHTA GIPING W/S Scheme | P2FBD139 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Tank not placed centre of ring beam, Improper levelling. | |||||||||||||
| 37 | 20023823 | Daudpur Majra Nandasa | P2FBD30 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Majority of nut bolt rusted and tank not vertically. | |||||||||||||
| 38 | 20023680 | Bhagaura W/S scheme | P2FBD71 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Flange nut bolt used whereas required washer nut bolt. | |||||||||||||
| 39 | 20023266 | Dullamai W/S Scheme | P2FBD25 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Majority of nut bolt rusted and tank not vertically. | |||||||||||||
| 40 | 20023669 | Kutubuddinpur W/S scheme | P2FBD70 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Flange nut bolt used whereas required washer nut bolt & improper levelling. | |||||||||||||
| 41 | 20023243 | Silsanda W/S Scheme | P2FBD63 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | DI pipe load in tank vertically downward. | |||||||||||||
| 42 | 8359376 | KUNDANGANESHPUR W/S SCHEME | P2FBD144 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Rusted nut bolts & Improper levelling. | |||||||||||||
| 43 | 20092874 | Jhaua MVS | P2FBD104 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Excessive rust has developed on the reinforcement in Raft. | ||||||||||||
| 44 | 20023282 | Lodhipur W/S Scheme | P2FBD182 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | Cube fail of OHT bottom slab required Ultrasonic Pulse Velocity. | ||||||||||||
| 45 | 20074354 | BAHORA SVS | P2FBD167 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | concrete pouring in 1st brace beam and found 20 mm aggregate with mixing unapproved materials. | ||||||||||||
| 46 | 20076393 | Moosa khiriya w/s scheme | P2FBD154 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 10mm aggregate with mixing unwanted material available at site during Raft concrete work. | ||||||||||||
| 47 | 8388559 | NAGLA KEWAL WS SCHEME | P2FBD208 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Substandard Quality of material are being used in OHT slab | ||||||||||||
| 48 | 20092660 | Sikandarpur Tihaiya MVS | P2FBD200 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | Cube fail of column above 2nd Brace Beam. | ||||||||||||
| 49 | 20092317 | Bilsari MVS | P2FBD195 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | Zi-Al slab (Bilsari ) cube not available in lab during testing required NDT Test. | ||||||||||||
| 50 | 20038943 | Faridpur Multi V w/s scheme | P2FBD74 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | 1st Brace beam cube not available in lab during testing required NDT test. | ||||||||||||
| 51 | 20023298 | Nadaura W/S Scheme | P2FBD27 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | Honeycomb found in 3rd brace beam. | ||||||||||||
| 52 | 20023203 | Mahmadganj W/S Scheme | P2FBD212 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | 20mm Extra bar not provided in OHT bottom reinforcement . | ||||||||||||
| 53 | 20023248 | Sahab Ganj W/S Scheme | P2FBD64 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | Honeycomb found 1st lift column. | ||||||||||||
| 54 | 20096551 | GADANPURA CHAIN MVS | P2FBD94 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Hold down bracket not installed vertically & Improper levelling and Tank not vertically align. | |||||||||||||
| 55 | 20023170 | Sharfabad W/S Scheme | P2FBD138 | Yes | No | No | No | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Above the 3rd brace at the 2nd lift columns (04 Nos.), honeycombing repair executed using cement paste is unacceptable and has resulted in surface cracking. . | |||||||||||
| 56 | 20023286 | Karhiyoli W/S Scheme | P2FBD66 | No | No | No | Yes | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Honeycombing and reinforcement exposure observed in one of the columns above the 2nd brace level. | |||||||||||
| 57 | 8359324 | KHETALPUR SORIYA W/S SCHEME | P2FBD176 | No | No | No | Yes | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Inadequate Concrete Cover in One Colum & Exposuer and Corrosion of Reinforcement, Shear key. | |||||||||||
| 58 | 20074314 | SULTANGANJ KHARETA SVS | P2FBD98 | No | No | No | No | Yes | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Raft beam casting without RFI & Found beam width 400-420 mm while required 500 mm as pe Approved drawing. | |||||||||||
| 59 | 20076419 | Kuiyan Sant w/s scheme | P2FBD110 | No | No | No | No | Yes | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Beam width less than Approved drawing. | |||||||||||
| 60 | 20020108 | Usmanganj W/S Scheme | P2FBD135 | No | Yes | No | No | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | The staircase was found tilted to one side and Beams (SB1) for the 1st and 2nd staircase landings have been placed along the face of the column instead of at the centerline of the column. | |||||||||||
| 61 | 20018367 | Allabal Pur W/S Scheme | P2FBD18 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Resolved | Hold down bracket not installed vertically and Majority of nut bolt found rusted. | ||||||||||||
| 62 | 8388562 | GOSARPUR W/S SCHEME | P2FBD11 | No | No | No | No | No | No | Yes | No | No | No | No | No | Yes | 1-Seepage in OHT Conical Wall and Crack Observed in Staircase Rest Slab. 2-OHT constructed within 100 meter of a water body.(Pond). | |||||||||||||
| 63 | 20092314 | Karanpur Majra Basmai MVS | P2FBD45 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Over Head Tank, it was observed that the OHT slab has covered more than 60% of the clear width of the final lift of the staircase,due to which the effective width and accessibility of the staircase has been reduced. | |||||||||||||
| 64 | 20038848 | Hisampur W/S scheme | P2FBD142 | Yes | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | Resolved | Severe honeycombing and reinforcement exposure noticed at the bottom surface of the 2nd and 3rd brace beams. | |||||||||||
| 65 | 20023238 | Ambar Pur W/S Scheme | P2FBD213 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | The riser and tread of the 1st and 2nd flight of the staircase have not been constructed as per the approved drawing, and the work was executed without raising any Request for Inspection | |||||||||||||
| 66 | 20076663 | Sultanpur Palnapur & Bhagipur Umrah W/S scheme | P2FBD205 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Resolved | Flange nut bolt used where as required washer nut bolt & improper levelling & rusted nut bolt. | ||||||||||||
| 67 | 20023290 | Antar W/S scheme | P2FBD214 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Dowel bars have not been provided for the staircase reinforcement anchorage, Misaligned column above 3rd brace. | |||||||||||||
| 68 | 20023300 | Balipur Majra Atseni W/S Scheme | P2FBD68 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Exposed Reinforcement and Major Honeycombing Observed in 2nd & 3rd Brace Beam | |||||||||||||
| 69 | 8359188 | HAIDARPUR | P2FBD118 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Resolved | Improper centering of ring beam & oversized lapping in corrugated sheet. | ||||||||||||
| 70 | 8359203 | BIDAIL W/S SCHEME | P2FBD120 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Resolved | Improper drilling in hold down bracket, rusted nut bolt & Tank not placed at the centre of ring beam. | ||||||||||||
| 71 | 20038840 | Shadnagar w/s scheme | P2FBD191 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Resolved | Tank not vertically & hold down bracket installed improper. | ||||||||||||
| 72 | 20018313 | BIBIPUR W/S Scheme | P2FBD133 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Resolved | Flange nut bolt used where as required washer nut bolt & improper levelling. | ||||||||||||
| 73 | 20019920 | Karamchand Pur W/S Scheme | P2FBD134 | No | No | No | No | No | Yes | No | No | No | No | No | No | Yes | Resolved | 1.Tank not placed centre of ring beam, Hold down bracket not vertically . 2. OHT constructed within 100 meter of water body (Pond) . | ||||||||||||
| 74 | 20076280 | Kanjhiyana mvs | P2FBD147 | No | No | No | No | No | Yes | No | No | No | No | No | No | Yes | 1.Improper levelling, Flange nut bolt used whereas required washer nut bolt. 2. OHT constructed within 100 meter of water body (Pond). | |||||||||||||
| 75 | 20023856 | BHIDAUR W/S SCHEME | P2FBD91 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | Honeycomb found 1st Brace. | ||||||||||||
| 76 | 8359200 | CHITAPUR KAPURAPUR W/S SCHEME | P2FBD160 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Cracks have developed in the staircase landing area, Rise & trade not as per drawing. | |||||||||||||
| 77 | 20091978 | Rai MVS | P2FBD216 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | 1. The RCC Ring Beam has been shifted inward by approximately 140 mm from the edge of all RCC columns. 2. The deviation is uniform around the entire circumference, indicating improper execution and positioning of the Ring Beam during construction. 3. The required opening for the staircase landing has not been provided in the Ring Beam as per the approved structural drawing | |||||||||||||
| 78 | 20024456 | Hansapur Gouraipur | P2FBD188 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Gap between tank sheet and RCC Ring Beam/Slab,Tank not installed at the centre of the Ring Beam,Tank not found in proper plumb. Improper fixing of Hold-Down Brackets. | |||||||||||||
| 79 | 8359212 | ALUPUR IKDARIYA W/S SCHEME | P2FBD121 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | 1. 80% bolts are heavily rusted trying to cover with paint. 2. Tank is out of plumb due to outward bulging at its center portion. | |||||||||||||
| 80 | 8388557 | DEVRANPUR GADIYA W/S SCHEME | P2FBD129 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | 1. The tank is not placed at the centre of the ring beam, and variations in measurements observed from the projection, recorded as 1000mm & 1300mm respectively. 2. 90% bolts are rusted trying to cover with paint. 3. Cracks observed on the staircase landing. | |||||||||||||
| 81 | 8360724 | ISHAPUR W/S SCHEME | P2FBD127 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | 1. Turbine vent found in damaged condition. 2. The tank is not placed at the centre of the ring beam, and variations in measurements observed from the projection, recorded as 1000mm & 1300mm respectively. 3. Leakage found at 3-4 location in tank. 4. Walkway damaged around the DI pipe fitting | |||||||||||||
| 82 | 8359217 | AHMADPUR DEWARIYA TUBEWELL | P2FBD122 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | 1. The tank is not placed at the centre of the ring beam, and variations in measurements observed from the projection, recorded as 950mm & 1500mm respectively. 2. Due to centre portion of the tank is bulging outward tank not in vertical alignment. 3. 90% bolts are rusted trying to cover with paint. | |||||||||||||
| 83 | 20021398 | Shekhpur Rustampur W/S Scheme | P2FBD137 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | 1. The opening provided for the DI pipe is larger than the required size. 2. The tank is not placed in the center of the ring beam, with variations in measurements observed from the projection, recorded as 1050 mm & 860mm respectively. 3. Tank erupted at multiple locations. | |||||||||||||
| 84 | 20016714 | Danmandi kamalganj W/S scheme | P2FBD132 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | 70% bolts are rusted trying to cover with paint | |||||||||||||
| 85 | 8359180 | JHASI W/S SCHEME | P2FBD116 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | 1. Major honey comb observed in the bottom slab & beam. 2. Walkway damaged around the DI pipe fitting. | |||||||||||||
| 86 | 8359165 | KAMALPUR W/S SCHEME | P2FBD113 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | 1. Leakage found at multiple locations. 2. Tank out of plumb due to outward bulging at its center portion. 3. 80% bolts are heavily rusted trying to cover with paint. | |||||||||||||
| 87 | 20074295 | PAIGUPUR SVS | P2FBD145 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | 1. As per drawing 760 GSM Liner used but as per SWSM guideline minimum 890 GSM liner shall be used. Letter no. 3129/Zn-Al/2025-26/UGT. | |||||||||||||
| 88 | 8359176 | UGARPUR SULTANPATTI W/S SCHEME | P2FBD114 | No | No | No | No | No | Yes | No | No | No | No | No | No | Yes | 1. Anode found in damaged condition. 2. Walkway damaged around the DI pipe fitting. 3. Tank is not in plumb, indicating a vertical alignment & Centre portion of the tank is bulging outward. 4. Corrugated Sheet bulging out on 2nd layer & 5.OHT constructed within 100 Meter of water body (Pond). | |||||||||||||
| 89 | 20023277 | Mahrupur Bijal W/S Scheme | P2FBD140 | No | No | No | No | No | Yes | No | No | No | No | No | No | Yes | 1. Walkway damaged around the DI pipe fitting. 2. Due to Center portion of the tank is bulging outward tank is not in plumb. 3.OHT constructed within 100 Meter of water body (Pond). | |||||||||||||
| 90 | 20097756 | Chachoopur Jatpura MVS | P2FBD227 | Yes | Yes | Yes | No | No | No | No | No | No | No | No | No | No | 1.Honeycomb 3rd & 4th brace beam, column misaligned above 1st brace. 2. 1st & 4th Brace beam Cube fail. | |||||||||||||