Agency-wise Major/critical Ncs at OHT

S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 20101892 Bhurepur PWS 20101892/01 No No Yes No No No No No No No No No Yes The cube test result for the final flight staircase of the OHT has been found to be failed. Also, the OHT of this scheme is located near the pond.
2 20100464 Babarpur Dehat PWS 20100464/01 No No No No No No Yes No No No No No No Resolved Minor misalignment was observed in one column located.
3 20084725 Turkpur Phaphoond PWS 20084725/01 No No Yes No No No No No No No No No No Resolved Cube test failure observed in the OHT structure; NDT was conducted for the 2nd lift column above the 2st brace.
4 20039855 Sondhemau PWS 20039855/01 No No Yes No No No No No No No No No No Resolved Cube test failure observed in the OHT structure; NDT was conducted for the 2nd lift column above GL.
5 20034858 khanpur phaphund 20034858/01 Yes No No No No No No No No No No No No Resolved honeycombing After rectification NDT was conducted for column blow of 1st brace beam, 2nd brace beam and bottom dome.
6 20084705 Auton PWS 20084705/01 Yes No No No No No No No No No No No No Resolved honeycombing After rectification NDT was conducted for the column above1st brace beam and 2nd brace.
7 20065627 Bhadsiya & bamrauliya 20065627/01 No No Yes No No No No No No No No No No Resolved 7-day cube test failed.
8 20040104 Aampur PWS 20040104/01 No No Yes No No No No No No No No No No Resolved Cube test of the bottom dome was found below acceptance criteria; NDT was conducted.
9 20087932 Mani kothi khash PWS 20087932/01 No No Yes No No No No No No No No No No Resolved Cube failure and NDT of 3rd flight staircase of OHT.
10 20041697 Kalabhoj 20041697/01 No No Yes No No No No No No No No No No Resolved Cube failure and NDT of 1st flight staircase of OHT.
11 20025457 JAMUHA PWS 20025457/01 No No Yes No No No No No No No No No No Resolved Cube failure and NDT of final flight staircase of OHT.
12 20093483 Sahbajpur bidhuna PWS 20093483/01 No No Yes No No No No No No No No No No Resolved Cube failure in OHT; NDT conducted for 3nd lift column above 2nd brace.
13 20095107 Sanwaliya PWS 20095107/01 No No Yes No No No No No No No No No No Resolved Cube failure in OHT; NDT conducted for 1st lift column above 3rd brace.
14 20099278 Puranpur & Manikpur 20099278/01 No No Yes No No No No No No No No No No Resolved Cube failure in OHT; NDT conducted for 1st lift column above 2nd brace.
15 20091164 Sarai pratham PWS 20091164/01 No No No No No No Yes No No No No No No Resolved Cube mould not available at site; NDT conducted for OHT container wall.
16 20088700 Kurshi PWS 20088700/01 No No Yes No No No No No No No No No No Resolved Cube failure and NDT of 3rd flight staircase of OHT
17 20064337 Rampur Khash PWS 20064337/01 No No Yes No No No No No No No No No No Resolved Cube test of the top dome was found below acceptance criteria. NDT was conducted
18 20091158 Dahiyapur PWS 20091158/01 Yes No No No No No No No Yes No No No No Resolved Resolved Columns of the OHT structure above GL were dismantled due to major honeycombing observed in all columns.
19 20099164 Barau PWS 20099164/01 No No Yes No No No No No No No No No No Resolved Cube failure and NDT of the 3nd brace of the OHT.
20 20087935 Punawar PWS 20087935/01 No No Yes No No No No No No No No No No Resolved Cube failure in OHT; NDT conducted of final lift column above 3rd brace.
21 20091156 Bhartaul 20091156/01 No No Yes No No No No No No No No No No Resolved Cube failure in OHT; NDT conducted of 1st lift column above 1st brace.
22 20093726 Bhadaura PWS 20093726/01 No No Yes No No No No No No No No No No Resolved Cube test of the bottom dome was found below acceptance criteria; NDT was conducted.
23 20093474 Barbatpur & juhikha 20093474/01 No No Yes No No No No No No No No No No Resolved Cube test of the top dome was found below acceptance criteria. NDT was conducted.
24 20065298 Nagla simar PWS 20065298/01 No No Yes No No No No No No No No No No Resolved Cube test of the container wall 1st was found below acceptance criteria. NDT was conducted.
25 20076359 Dalel Nagar PWS 20076359/01 No No Yes No No No No No No No No No No Resolved Cube test of the container wall 1st lift was found below acceptance criteria. NDT was conducted.
26 20084702 Nurabad khash PWS 20084702/01 No No Yes No No No No No No No No No No Resolved Cube test of the bottom dome was found below acceptance criteria. NDT was conducted.
27 20089664 Barmupur PWS 20089664/01 No No Yes No No No No No No No No No No Resolved Cube test of the top dome was found below acceptance criteria. NDT was conducted.
28 20093727 Baraua PWS 20093727/01 No No Yes No No No No No No No No No No Resolved Cube failure in OHT; NDT conducted for 1st lift column above Raft beam.
29 20093432 Malhausi 20093432/01 No No Yes No No No No No No No No No No Resolved Cube failure in OHT; NDT conducted for 1st lift column above 2nd brace.
30 20084717 Gauri ganga prasad 20084717/01 No No Yes No No No No No No No No No No Resolved Cube test of the top dome was found below acceptance criteria. NDT was conducted.
31 20088690 Udaipur PWS 20088690/01 No No Yes No No No No No No No No No No Resolved Cube test of the container wall was found below acceptance criteria. NDT was conducted.
32 20091159 Lohiyapur PWS 20091159/01 No No Yes No No No No No No No No No No Resolved Cube test of the container wall 1st lift was found below acceptance criteria. NDT was conducted.
33 20084698 Lahtoria PWS 20084698/01 No No Yes No No No No No No No No No No Resolved Cube test of the bottom dome was found below acceptance criteria. NDT was conducted.
34 20091122 Kakrahi 20091122/01 No No No No No No Yes No No No No No No Resolved Cube mould not available at site; NDT conducted for OHT bottom dome.
35 20095133 Umarsana PWS 20095133/01 No No No No No No Yes No No No No No No Resolved Cube mould not available at site; NDT conducted of 6th flight staircase of OHT.
36 20065288 Piparpur PWS 20065288/01 No No Yes No No No Yes No No No No No No Resolved Resolved Cube mould not available at site; therefore, NDT was conducted for the OHT bottom dome. Also, due to cube failure, NDT was conducted for the 6th flight staircase of the OHT.
37 20064338 Rawat pur& Shivpur PWS 20064338/01 No No Yes No No No No No No No No No No Resolved Cube test of the container wall was found below acceptance criteria; NDT was conducted.
38 20041740 Siryawa 20041740/01 No No Yes No No No No No No No No No No Resolved Cube test of the bottom dome was found below acceptance criteria; NDT was conducted.
39 20089653 Walidadpur PWS 20089653/01 No No Yes No No No No No No No No No No Resolved Cube failure and NDT of final flight staircase of OHT.
40 20091180 Bharrapur PWS 20091180/01 No No Yes No No No No No No No No No No Resolved Cube test of the bottom dome was found below acceptance criteria; NDT was conducted.
41 20089657 Ajuapur PWS 20089657/01 No No Yes No No No No No No No No No No Resolved Cube test of the bottom dome was found below acceptance criteria; NDT was conducted.
42 20091176 Sarai Tadawa 20091176/01 No No Yes No No No No No No No No No No Resolved Cube test of the bottom dome was found below acceptance criteria; NDT was conducted.
43 20099287 Birpur PWS 20099287/01 No No Yes No No No No No No No No No No Resolved Cube test results of the 1st brace beam were found below the acceptance criteria; therefore, NDT was conducted.
44 20041737 RURUA PHAPHUND PWS 20041737/01 No No Yes No No No No No No No No No No Resolved Cube failure and NDT of 1st and 2nd flight staircase of OHT.
45 20065264 Antol PWS 20065264/01 No No Yes No No No No No No No No No No Resolved Cube test of the container wall 2nd lift was found below acceptance criteria; NDT was conducted.
46 20099280 Ghasara PWS 20099280/01 No No Yes No No No No No No No No No No Resolved Cube test of the container wall 2nd lift was found below acceptance criteria; NDT was conducted.
47 20084724 Jalalpur phaphund PWS 20084724/01 No No Yes No No No No No No No No No No Resolved Cube failure in OHT; NDT conducted for 1st lift column above 2nd brace.
48 20091138 Dakhnai PWS 20091138/01 No No Yes No No No No No No No No No No Resolved Cube test of the container wall 2nd lift was found below acceptance criteria; NDT was conducted.
49 20084711 Chandauli PWS 20084711/01 No No Yes No No No No No No No No No No Resolved Cube failure and NDT of 3rd flight staircase of OHT.
50 20099286 Iqbal pur PWS 20099286/01 No No Yes No No No No No No No No No No Resolved Cube test of the container wall 1st lift was found below acceptance criteria; NDT was conducted.
51 20065255 Ballpur Rajpur 20065255/01 No No Yes No No No No No No No No No No Resolved Cube test of the bottom dome was found below acceptance criteria; NDT was conducted.
52 20065633 Chapta PWS 20065633/01 No No Yes No No No No No No No No No No Resolved Cube test of the top dome was found below acceptance criteria; NDT was conducted.
53 20091172 Bighepur PWS 20091172/01 No No Yes No No No No No No No No No No Resolved Cube failure and NDT of final flight staircase of OHT.
54 20091149 Bailipur PWS 20091149/01 No No No No Yes No No No No No No No No Resolved The rise, tread, and slab thickness of the 4th and 5th flight staircases of the OHT were not as per the drawing. The rectification work has been carried out.
55 20084720 Alipur & Puttha PWS 20084720/01 No No No No No No Yes No No No No No No Resolved The 7th flight staircase of the OHT was cast without steel checking. Although the RFI was raised, by the time the inspection team reached the site, the casting work was almost completed. NDT (Rebound Hammer & UPV) has been done.
56 20039871 Murainaram Dutt PWS 20039871/01 No No Yes No No No No No No No No No No Resolved Cube failure in OHT; NDT conducted for 2nd lift column above 1st brace.
57 20038717 SLLAHPUR 20038717/01 Yes No No Yes No No No No Yes No No No No Resolved Resolved Resolved The bottom dome was dismantled due to major honeycombing and exposed reinforcement.
58 20100460 Alpi PWS 20100460/01 No No Yes No No No No No No No No No No Resolved Cube test of the top dome was found below acceptance criteria. NDT was conducted.