Agency-wise Major/critical Ncs at OHT

S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 20085094 BHABHANGAWA KHURD GP wss 20085094/01 No Yes No No No No No No No No No No No OHT staircase work not done properly
2 20085066 SUMAHI GP wss 20085066/01 No No Yes No No No No No No No No No No OHT staircase cube test
3 20102388 MARWATIYA GP wss (J) 20102388/01 No No Yes No No No No No No No No No No As per the test results, the compressive strength achieved is 25.68 N/mm², against the specified strength of 30.00 N/mm².
4 20102389 BABHAN GANWA GP wss (J) 20102389/01 No Yes No No No No No No No No No No No OHT 1st brace beam & 1st lift column
5 20085061 GUWANA GP wss 20085061/01 No Yes No No No No No No No No No No No 1. Column reinforcements not meets lapping zone requirements. 2. Column steel rusted . 3. Reinforcements of OHT column lapping not meets IS 456:2000 & IS 13920 specifications.
6 20102406 RANIPUR GP wss (J) 20102406/01 No No No No No No Yes No No No No No No Resolved