Agency-wise Major/critical Ncs at OHT

S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 20024072 Sarai Madansingh Urf Chanti single village water supply scheme LP-59 No No No No No No No No No No No No No The OHT is constructed with in 100 mtr range from Pond
2 8388580 Babahan Kuseyan Gram Panchayat LP-405 No No No No No Yes No No No No No No No Resolved ZN / AL Tank found leakage
3 8362702 BANI GRAM PANCHAYAT WATER SUPPLY SCHEME LP-398 No No No No No Yes No No No No No No No Resolved ZN / AL Tank found leakage
4 8362461 BHOPAT PUR GRAM PANCHAYAT WATER SUPLY SCHEME LP-397 No No No No No Yes Yes No No No No No No Resolved Resolved The alignment of the inlet and outlet pipes for the water tank is not vertical it needs immediate correction to ensure they are properly aligned.
5 20057152 Devkali multi village water supply scheme LP-236 No No No No No No Yes No No No No No No Resolved It has been observed that cracks have been found in the top surface of OHT raft.
6 20023951 Dewariya MVS scheme LP-230 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. Water will seepage inside the foundation and cause excessive settlement.
7 20100451 KAITHWAL WATER SUPPLY SCHEME LP-465 No No No No No No Yes No No No No No No Resolved Rainwater has accumulated on the raft of the overhead tank (OHT). This water can seep into the foundation, potentially causing excessive settlement.
8 8361287 LILAPUR KLA GRAM PNACHAYAT WATER SUPPLY SCHEME 8361287/01 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the Foundation of OHT. Water will seepage inside the foundation and cause excessive settlement.
9 20094827 RAMNAGER-MIRAPUR-CHANDERPUR URF BUSMAHUA WATER SUPPLY SCHEME LP-390 No No No No No No Yes No No No No No No Resolved As per drawing overlapping should be maintained 46 D (552 mm) while overlapped found only 275 mm at site.
10 8361286 SEMRA MULTI VILLAGES WATER SUPPLY SCHEME LP-82 No No No No No No Yes No No No No No No Resolved During the site inspection of OHT, it was found that water is entering from the upper section, which could lead to leakage or seepage issues.
11 20088072 CHANDRAWAT URF POORE MATADIN_SARAI SULTAN URF MAKHDOO WATER SUPPLY SCHEME LP-300 No No No No No No Yes No No No No No No Resolved as per visual inspection crack has been observed on the OHT's H - frame beam.
12 8360352 JAMHA GRAM PANCHAYAT WATER SUPPLY SCHEME LP-536 No No No No No No Yes No No No No No No Resolved Shear link has not been bent at 135 degree and not bounded to the bottom reinforcement properly.
13 8360642 SARAI MADAN MULTI VILLAGES WATER SUPPLY SCHEME LP-25 No No No No No Yes Yes No No No No No No Resolved Resolved Leakage has been found in ZA tank
14 20085207 SARAIDATTE WATER SUPPLY SCHEME LP-370 No No No No No No Yes No No No No No No Resolved as per visual inspection crack has been observed on H - frame's column and it may be propagate during loading condition.
15 20065320 Tejpur multi village water supply scheme LP-211 No No No No No No Yes No No No No No No Resolved OHT Raft upto beam top bar is not binding straight C/C as per drawing. Rusted steel bar is being used on the site. Rust should be cleaned before casting.
16 20034830 Arhani Single Village Water Supply Scheme LP-240 No No No No Yes No No No No No No No No Resolved According to the Design and Drawing with DPR (BOQ) 125 KL 12 M capacity OHT has been constructed instead of 125 KL 14 M. But due to change in location and change in design and drawing, the level of the OHT has gone down also. The place where the tank should be given is from the road level or it is given from the GL.
17 20034917 Bahupur Multi Village Water Supply Scheme LP-157 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
18 20097469 BANPURAWA SARAIPITHA WATER SUPPLY SCHEME LP-216 No No No No No No Yes No No No No No No Resolved crack has been observed in The column of OHT. Diagonal crack has been observed at the surface of H-frame beam of OHT.
19 20038865 Bibipur Multi Village Water Supply Scheme LP-53 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
20 20034925 Gaharpur Dhobaha Single Village Water Supply Scheme LP-441 Yes No No Yes No No No No No No No No No Resolved Resolved Steel bars has been exposed on the surface of OHT raft and honeycomb also observed.
21 20034759 Jaraon SIngle Village water supply scheme LP-206 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
22 20100313 KALANA WATER SUPPLY SCHEME LP-228 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. Water will seepage inside the foundation and cause excessive settlement.
23 20100331 KESHAW RAIPUR WATER SUPPLY SCHEME LP-209 No No No No No No Yes No No No No No No Resolved The water filled has been found in OHT bottom surface area. Due to this settelment may be happen in future
24 20058700 Khirjipur and Makadumpur Multi Village water Supply Scheme LP-261 No No No No No No Yes No No No No No No Resolved Rain water has accumulated on the backfill soil of HOT. Water will seep into the foundation and cause excessive settled.
25 20017790 KIRAON VILLAGE WATER SUPPLY SCHEME LP-208 No No No No No No Yes No No No No No No Resolved Lap length of steel bar has been found 450 mm however as per drawing 570 mm. C/C spacing of shear stirrups have been found 210 mm however as per drawing 150 mm.
26 20024453 Kundanpur Multi Village Water Supply Scheme LP-244 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
27 20065456 Mavaiya Hindubani Multi Village water supply scheme LP-259 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
28 20089052 PARAWA WATER SUPPLY SCHEME LP-223 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
29 20024459 Pipri Amadbhadoh Multi VIllage Water Supply Scheme 20024459/01 No No No No No No Yes No No No No No No Resolved The water filled has been found in OHT bottom surface.
30 20095031 PURE SADA BHAMA_MAHARAJPUR WATER SUPPLY SCHEME LP-270 Yes No No No No No No No No No No No No Resolved Severe honeycomb has been observed at the pedestal and plinth beam of OHT. Kindly conduct NDT test to ensure their strength or reconstruct it if found unsatisfactory results.
31 20023950 Shripur village water supply scheme LP-130 No No No No No No Yes No No No No No No Resolved Rusted reinforcement MS steel has been found on Raft foundation. Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
32 20086751 THARIYA_NIMI WATER SUPPLY SCHEME LP-279 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
33 20085538 VANPURWA PARATIPUR_MAHAJANA WATER SUPPLY SCHEME LP-446 No No No No No No Yes No No No No No No Resolved The water filled in the OHT bottom surface area.
34 20026262 Yasinpur (Pasiyapur) Multi Village Water Supply Scheme 20026262/01 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. Water will seepage inside the foundation and cause excessive settlement. Work has been stopped for many days due to this steel bars are getting rusted.
35 20023402 Awasanpur single village water supply scheme LP-304 No Yes No No No No No No Yes No No No No Resolved Resolved The alignment of 2nd lift column has not been found properly vertical. Dismantle the column and reconstruct it.
36 20097292 BALA WATER SUPPLY SCHEME LP-323 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
37 20085284 DUBAKI KURD WATER SUPPLY SCHEME LP-68 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
38 20024652 Gondaura Bilari Multi Village Water Supply Scheme LP-301 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
39 20023399 Harchandpur mukti village water supply scheme LP-65 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
40 20021069 Jagua Sodha village water supply scheme LP-11 No No No No No Yes No No No No No No No Resolved The Zink aluminium tank nuts and bolt have not tightened properly.
41 20094972 JHIRHARI_BAGAHA WATER SUPPLY SCHEME LP-333 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
42 8360728 KISHUNIPUR GRAM PANCHAYAT MULTI VILLAGESWATER SUPPLY SCHEME 8360728/01 Yes Yes No No No No No No Yes No Yes No No Resolved Resolved Resolved Resolved After visiting the site, a Honeycomb Structure has been found in OHT Column. The alignment of column no.3rd above first brace beam has been found misaligned. Dismantle the column and reconstruct it again.
43 20064807 Pure Gobai and Chhini Gram Panchayat MVS LP-359 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement. Steel bars are submerged in the water.
44 20085277 PURE MATHURADAS WATER SUPPLY SCHEME LP-360 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
45 20086760 SIDHAWAR HARIPUR WATER SUPPLY SCHEME LP-312 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
46 20018236 SUARA VILLAGE WATER SUPPLY SCHEME LP-15 No No No No No No Yes No No No No No No Resolved The leakage has been found form the DI pipeing in the OHT
47 20024657 Arjunpur & Bujha Multi Village Water Supply Scheme LP-193 No No No No No No Yes No No No No No No Resolved Various cracks has been developed on the top surface of the secondary beam of OHT. Kindly rectify it or replace.
48 20020791 Barai Harakh Water Supply Scheme LP-503 Yes No No Yes No No Yes No No No No No No Resolved Resolved Resolved Cracks have been started developing in the four columns of OHT. It may be due to lack of curing and environmental effects. Kindly rectify it as soon as possible. Poor workmanship has been observed in the concrete work of 1st lift column. Steel bar shown after casting. kindly do needful action to rectify this. Honeycombing has been found in OHT beam lintel casting work. Honeycombing has been found in OHT beam lintel casting work. Poor quality of 10 mm aggregate has been stacked at site for construction of OHT members. Kindly remove this material from site. Oversized and poor quality of 20 mm coarse aggregate has stacked at site for construction of OHT members. kindly remove these materials from site immediately. steel bars of OHT column have been affected by corrosion. Flaky and elongated aggregates has been stacked at site for concreting of OHT staging work. NC was raised but compliance has not been done. Construction work has been stopped for more than three months. Due to which, Steel bars are getting rusted. Two column of OHT at plinth level has been observed bulged. cover was not maintained at the column. 40 mm cover should have been provided to the steel bar. Kindly dismantle the columns and reconstruct properly.
49 20025873 Dahiyawan single multi village scheme LP-149 No No No No No Yes No No No No No No No Resolved Leakage has been occurred from ZA tank of OHT. Take corrective action immediately.
50 20023057 Girdharpur Gondawa village water supply scheme LP-147 No No No No No No Yes No No No No No No Resolved rain water has been accumulated inside the trench of Raft. Settlement may occur and cause of severe damaged. Kindly remove water and fill it immediately.
51 20092099 JADOPUR WATER SUPPLY SCHEME LP-337 No No No No No No Yes No No No No No No Resolved A Crack has been observed on the precast H- Frame.
52 20088578 KAMALPUR_FATEHPUR TA. SHAHABPUR WATER SUPPLY SCHEME LP-338 Yes No No No No No No No No No No No No Resolved Honeycomb has been observed at the junction of the 2nd lift column and beam. And also after removal of form work finishing was not done.
53 20065199 Kasturipur Multi Village Water Supply Scheme LP-191 No No No No No No Yes No No No No No No Resolved Alignment of the pedestal of OHT have not been observed properly. Dowel bars have not been placed concentrically. it may results eccentric load distribution and may collapsed. Take appropriate action immediately before erection work of precast members. Two Pedestal of OHT has not casted in proper alignment and also one of them has bulged. Cracks have been started developing on the 1st brace precast column of OHT. Kindly take corrective action regarding this.
54 20024071 Sarai Bharat urf Holagarh single village water supply scheme LP-100 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated inside the trench of Raft. It may cause excessive settlement of soil. Hair line cracks have been observed on the surface of H frame of OHT.
55 20097472 SARAI SAHEB WATER SUPPLY SCHEME LP-60 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. It may cause settlement of foundation.
56 20065728 Sultanpur jaisingh Multi village water supply scheme LP-178 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. It may cause settlement of foundation.
57 20024054 Bhagesar Dehli Multi village water supply scheme LP-241 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
58 20100407 BHATHERAWA WATER SUPPLY SCHEME LP-72 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
59 20094976 DANDO_MACHAHAR URF PURWA WATER SUPPLY SCHEME LP-350 No No No No No No Yes No No No No No No Resolved Steel bars of OHT raft are getting rusted. reinforcement of raft has been completed but casting work has been pending for more than one month.
60 20024505 Harrai Multi village water supply scheme LP-425 Yes No No No No No No No No No No No No Resolved honeycombs has been observed in the column of OHT, the compaction of the concrete mass by capturing air gaps and preventing honeycomb should be done during concrete casting Ref. IS 456:200 Clause 13.3.1.
61 20037187 Kaithi Single Village Water Supply Scheme LP-110 No No No No No No Yes No No No No No No Resolved The shear links have been provided inclined (which cannot contribute against shear resistance). The Shear link should be vertical as per approved design & drawing also Refer of IS 456:2000 Clause-26.2.2.4 (b). c/c spacing of Shear stirrups have not been provided uniformly as per drawing. and also the hooks of shear stirrups should be provided staggerd to eachother. Kindly rectify it before casting. The development length of steel bar should be provided inside to main bar of columns so that proper cover will maintain to the column. steel bar has been found rusted. Kindly clean it by sand paper before casting.
62 20097350 MAGHUWA WATER SUPPLY SCHEME LP-469 No No No No No No Yes No No No No No No Resolved Crack has been observed in H frame beam of OHT.
63 20024517 Nindauri Narayana Multi Village Water Supply Scheme LP-166 No No No No No No Yes No No No No No No Resolved Main top bars spacing has been found 170mm c/c at many places, as per drawing main bar should be 150mm c/c on site.
64 20032123 Pach Dewra Village Water Supply Scheme LP-104 No No No No No No Yes No No No No No No Resolved Spacing of top main bar has been found 180 mm instead of the 150 mm as per drawing.
65 20038857 Purani Multi Village Water supply scheme LP-69 No No No No No No Yes No No No No No No Resolved 25 mm cover block has been used instead of 50 mm at the side face of the raft. shear link has not been bound properly in the raft. Alignment of 32 mm bar has not been found properly. Rectify it before casting of raft.
66 20093239 ROKARI WATER SUPPLY SCHEME LP-180 Yes No No No No No No No No No Yes No No Resolved Resolved Honeycomb has been found in the side face of OHT raft foundation.
67 20092562 Sonai Water Supply Scheme LP-463 No No No No No No Yes No No No Yes No No Resolved Resolved Rusted bar observed at the piling site. Anti-correcive treatment before casting work required.
68 20100426 AKBARPUR MIRZAPUR WATER SUPPLY SCHEME 20100426/01 No No No No No Yes No No No No No No No Resolved
69 20097698 FOOL NAGAR_BISOUNA WATER SUPPLY SCHEME 20097698/01 No No No No No No Yes No No No No No No Resolved Crack has been found at the surface of slab of OHT.
70 20057185 Iguwa Urf Kathgawan Multi Village Water Supply Scheme LP-190 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. It may cause settlement of foundation.
71 20058922 Judapur Jhinhar Urf Bariboj multi village water supply scheme LP-114 No No No No No No Yes No No No No No No Resolved Level of PCC of OHT foundation has not been found properly. This should be rectified immediately before preparation of Raft reinforcement. Level of PCC base should be correct for uniformly load distribution.
72 20097482 KURESER UPERHER WATER SUPPLY SCHEME LP-117 No No No No No No Yes No No No No No No Resolved Rainwater has been accumulated over the Backfilled soil of OHT foundation. Kindly ensure proper Backfilling so that water cannot be accummulate. Otherwise it may seepage inside the foundation and causes uneven settlement. Crack has been observed on the surface of 1st H-frame brace. This crack has been observed more than 0.3 mm.
73 8360336 MARUFPUR GRAM PANCHAYAT WATER SUPPLY SCHEME 8360336/01 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated inside the Raft trench. Steel bar is getting rusted due to poor working condition. Kindly drain out the water and make proper arrangement for plinth beam reinforcement.
74 8360337 MENDARA GRAM PANCHAYAT WATER SUPPLY SCHEME LP-134 No No No No No No Yes No No No No No No Resolved The shear links of the raft are not properly connected to the bottom reinforcement and the shear links are also not tied vertically. This has already been mentioned in the RFI.
75 20097384 MERAPUR TALUKA AMAHADPUR WATER SUPPLY SCHEME 20097384/01 No No No No No No Yes No No No No No No Resolved Cracks has been started developing in the 1st lift column of OHT. Kindly take corrective action regarding this issues.
76 20094506 PEER DALLU_HUSENPUR WATER SUPPLY SCHEME LP-325 No No No No No No Yes No No No No No No Resolved Shear links of raft have not been bounded properly to the bottom reinforcement. And also shear links have observed inclined instead of vertical. Mud has been accumulated on the surface of pcc and bottom steel bar is getting rusted. Kindly take corrective action.
77 20100458 ANTAR SAMDARIYA (PEERI) WATER SUPPLY SCHEME LP-548 No No No No No No Yes No No No Yes No No Resolved Incomplete concrete construction had been done on the raft foundation. Dismantle the complete raft and reconstruct it properly by using fresh steel bars.
78 20095003 BARAHA-NIRAUNDHA WATER SUPPLY SCHEME LP-458 No No No No No No Yes No No No No No No Resolved Crack has been observed at brace beam of OHT
79 20023961 Dhondhari MVS water supply scheme LP-346 No No No No No No Yes No No No No No No Resolved Water has been accumulated over raft of OHT please remove immediately.
80 20065447 Kuaan Multo village Water supply scheme LP-456 No No No No No No Yes No No No No No No Resolved Water has been filled in the trench of OHT foundation. It will Leeds excessive settlement. Remove water and complete substructure work.
81 8360333 LAKHRAWAN GRAM PANCHAYAT WATER SUPPLY SCHEME LP-108 No No No No No No Yes No No No No No No Resolved Shear stirrups has not been provided properly.
82 20097355 MAGHIGAWA WATER SUPPLY SCHEME LP-121 No No No No No No Yes No No No No No No Resolved Diagonal shear crack has been developed at the side face of H -frame beam of OHT.
83 20089047 MAHI WATER SUPPLY SCHEME LP-549 No No No No No No Yes No No No Yes No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
84 20024228 Panwari single village water supply scheme LP-459 No No No No No No Yes No No No Yes No No Resolved Resolved Rain water has been accumulated over the foundation of OHT. Water will seepage inside the foundation and cause excessive settlement.
85 20024230 Pawar single village water supply scheme LP-377 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. Water will seepage inside the foundation and cause excessive settlement.
86 20086817 SEHRA WATER SUPPLY SCHEME LP-345 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
87 20059076 Semri Multi Village Water Supply Scheme 20059076/01 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the raft of OHT. Water will seepage inside the foundation and cause excessive settlement.
88 20065904 BISHAMBHERPUR GRAM PANCHAYAT Multi village scheme LP-48 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. It may cause settlement of foundation.
89 20065316 Gadiyani single village water supply scheme LP-51 No No No No No No Yes No No No No No No Resolved Water has been accumulated over the Backfilled soil of the OHT foundation.
90 20021112 Jamkhuri village water supply scheme LP-55 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. It may cause settlement of foundation.
91 20059214 Kathwer Perwaizpur Multi Village Water Supply Scheme LP-265 No No No No No No Yes No No No No No No Resolved Precast Slab panel of OHT has been found damaged at site. Kindly do not use this panel during erection. Various cracks have been observed on Pre-cast H-frame (1st lift). Kindly replace this H-frame.
92 20024766 Mahraunda Single Village Water Supply Scheme LP-388 No No No No No No No No No No No No No Rain water has been accumulated over the foundation of OHT. It may cause settlement of foundation. Rein water has been collected in the pit of raft. Steel bars are submerged in the water due to this bars are getting rusted. Remove it immediately and start reinforcement work of raft foundation.
93 20049449 Mani Umarpur multi village water supply scheme LP-85 No No No No No No Yes No No No No No No Resolved Water has been accumulated over the raft surface.
94 20025911 Purkhipur village water supply scheme LP-171 No No No No No No Yes No No No No No No Resolved Water has been accumulated over the Backfilled soil of the OHT foundation.
95 20022329 Ramnagar Gansiari village water supply scheme LP-283 No No No No No No Yes No No No Yes No No Resolved Resolved Pedestal steel bars of OHT have been severely rusted due to rain water and mud accumulation over the raft.
96 20021699 Sarai Atan urf Naugira MVS water supply scheme LP-74 No No No No No No Yes No No No No No No Resolved Rusted steel bar has been found for reinforcement of plinth beam and pedestal. Pilling depth above NGL less than 500mm
97 20038803 Sultanpur Khas Single Village Water Supply Scheme LP-129 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. It may cause settlement of foundation.
98 8360804 Akdala Gram Panchayat Multi Villages Water Suply Scheme LP-290 No Yes No No No No No No Yes No No No No Resolved Resolved Due to water logging on the foundation surface of the OHT, there may be a lot of problems in the future in case of Precast Structure. The alignment of the column in the OHT is not properly. Brace Beam has been found cracks.
99 20059239 Balkaranpur mai Kasarwae Multi Village Water Supply Scheme LP-160 No No No No No No Yes No No No No No No Resolved Crack has been observed on the surface of H-frame of OHT.
100 20097340 CHAK MOHAMD URF POORESOOD WATER SUPPLY SCHEME LP-513 No No No No No No Yes No No No No No No Resolved Water has been accumulated over the foundation of OHT. It may causes uneven settlement of foundation.
101 8362687 CHAQ SEKH AHMED URF KUSEHTA LP-317 No No No No No No Yes No No No No No No Resolved Development length of Main bar (32 mm dia.) of pedestal has not been provided properly. Ref. IS 456 It has been observed 32 mm dia. bar directly placed on PCC surface.
102 8362549 DHOKARI GRAM PANCHAYAT WATER SUPPLY SCHEME LP-292 No No No No No No Yes No No No No No No Resolved Water has been accumulated over the foundation of OHT. It may causes uneven settlement of foundation.
103 20059248 Herbhanpur multi village water supply scheme LP-316 No Yes No No No No No No No No Yes No No Resolved Resolved as per visual inspection miss alignment has been observed on the H- frame's column & proper finishing also not done. Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement. Crack has been observed at the side surface of primary beam of OHT.
104 20059260 Jagdev urf barethi, Manethu and Umari Maitatehara multi village water supply scheme LP-282 Yes No No No No No No No No No Yes No No Resolved Resolved as per visual inspection honeycomb has been observed at joint of the OHT column.
105 20024647 Kasarawe May Chakoliya Village Water Supply Scheme LP-481 No No No No No No Yes No No No No No No Resolved Corners of Brace Beam has been found damaged and Finishing & Grouting of H frame has not been done properly.
106 20094943 LILHAT WATER SUPPLY SCHEME LP-483 No No No No No Yes No No No No No No No Resolved Leakage has been found in ZA tank from past 15 days. resolved
107 20097336 MOHAMADABAD URF MIALWAN WATER SUPPLY SCHEME LP-529 No No No No No No Yes No No No No No No Resolved as per visual inspection Multiple cracks has been observed on the OHT H - frame beam.
108 20023946 Mubarakpur Multi VIllage Water Supply Scheme LP-484 No No No No No Yes No No No No No No No Resolved Leakage has been found in ZA tank from past 20 days.
109 20024775 Sauraha Single Village Water Supply Scheme LP-22 No No No No No No Yes No No No No No No Resolved Water logging on the foundation surface of the OHT, there may be Settlement occur in future
110 8360818 SHEFKHANPUR MAI CHAQSALIKMULTI VILLAGES WATER SUPPLY SCHEME LP-61 No No No No No Yes Yes No No No No No No Resolved Rain water has been accumulated over the backfill soil of overhead tank. Water will seepage inside the foundation and cause excessive settlement. Crack has been observed on the surface of h-frame of OHT.
111 20065703 Basana Khas- Jamua Multi Village water supply scheme LP-86 No No No No No No Yes No No No Yes No No Resolved Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
112 20024364 Chhatauna Multi Village WaterSupply Scheme LP-185 No No No No No No Yes No No No Yes No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
113 20087124 DALAPATPUR_BARIYARI WATER SUPPLY SCHEME LP-176 No No No No No No Yes No No No Yes No No Resolved Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
114 20024371 Khanpur Dandi single village water supply scheme LP-140 No No No No No No Yes No No No Yes No No Resolved Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
115 20097668 PURE VIKARAM SHAH WATER SUPPLY SCHEME LP-440 No No No No No No Yes No No No Yes No No Resolved Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
116 20023942 Rastipur village water supply scheme LP-109 No No No No No No Yes No No No Yes No No Resolved Resolved Rain water has been accumulated over the backfill soil of over head tank. Water will seepage inside the foundation and cause excessive settlement.
117 20030599 Sadarepur Multi Village Water Supply Scheme LP-447 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
118 20025876 Sarai Mamarej Single village water supply scheme LP-67 No No No No No No Yes No No No No No No Resolved The OHT column(C5) has been found cracked.
119 20085524 SEMARI WATER SUPPLY SCHEME LP-431 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
120 20065834 Sewana-Golawa gram panchayat water supply scheme LP-37 No No No No No No Yes No No No Yes No No Resolved Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
121 20065890 Thanapur-Thata Multi village Water Supply Scheme LP-31 No No No No No No Yes No No No Yes No No Resolved Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
122 20086875 UGAPUR WATER SUPPLY SCHEME LP-383 No No No No No No Yes No No No No No No Resolved Crack was not repaired properly by using specified material. Crack has been started developing again on the side surface of H-frame of OHT.
123 20092567 Ahirai Water Supply Scheme LP-372 No No No No No No Yes No No No No No No Resolved Water logging may occurred on foundation of OHT. There may be settlement occur in future.
124 20085518 BAGAI KHURD WATER SUPPLY SCHEME LP-534 No No No No No No Yes No No No No No No Resolved In the upper reinforcement the bars rods have completely rusted and soil has settled on the surface, it needs to be completely removed and rectified before casting.
125 20077760 KANAUJA KHURD_KANAUJA KLA_JAFERPUR URF BABUGANJ WATER SUPPLY SCHEME LP-308 No No No No No No Yes No No No No No No Resolved The top main bar of OHT slab reinforcement work found not verical at site Overlapping should be maintain 46 dia of bar as per drawing instead of 320 to 350 mm at site.
126 20097329 ROODAPUR WATER SUPPLY SCHEME LP-36 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfill soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
127 20093463 DADUPUR_DHUDEHRI_BENIPUR WATER SUPPLY SCHEME LP-524 No No No No No No Yes No No No Yes No No Resolved Resolved Water logging has been occurred over the foundation of OHT. Steel bars have been submerged in the water and getting ruated.
128 20024448 JALALPUR KASBA VILLAGE WATER SUPPLY SCHEME LP-416 Yes No No No No No No No No No No No No Resolved Severe Honeycomb has been observed on the side face of raft foundation.
129 20065841 Maharupur gram panchayat multi village water supply scheme LP-551 Yes No No No No No Yes No No No No No No Resolved Resolved Severe Honeycomb has been observed on the side face of raft foundation. Main bar (16 mm) has been placed above distribution bar (12 mm) in the reinforcement of raft. Kindly rectify it immediately as per drawing. Rainwater has accumulated on the raft of the overhead tank (OHT). This water can seep into the foundation, potentially causing excessive settlement.
130 20061107 Parsottampur multi village water supply scheme LP-328 No No No No No No Yes No No No No No No Resolved As per the visual inspection corner of the First (H frame) found the crack of the corner side.
131 20095001 SADIA BARAUNA_PATTIRAM WATER SUPPLY SCHEME 20095001/01 No No No No No No Yes No No No No No No Resolved Plinth beam of OHT has been damaged due to this steel bars have been exposed at damaged place.
132 20046779 Samodhipur Single Village Water Supply Scheme LP-522 Yes No No No No No No No No No Yes No No Resolved
133 20089045 BALKARANPUR WATER SUPPLY SCHEME LP-03 No No No No No No Yes No No No No No No Resolved Crack has been observed on the surface of OHT first lift H-frame. Kindly take corrective action regarding this. And also conduct NDT test on cracked members to ensure their strength. Various cracks has been observed on the surface first lift H-frame brace. These cracks may propogate after loading condition. So take corrective action regarding this.
134 20094932 BANKAT WATER SUPPLY SCHEME LP-424 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated inside the OHT foundation trench. it may causes execive settlement of soil. kindly Backfill it immediately.
135 20066051 Judapur Dandu Water Supply Scheme LP-382 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated inside the OHT foundation trench. It may causes execive settlement of soil. Kindly Backfilled the foundation trench immediately.
136 20065219 Lakanpur Multi Village Water Supply Scheme 20065219/01 No No No No No No Yes No No No No No No Resolved Cracks have been observed in the precast H-frame.
137 20065829 Mohammadpur naugawan water supply scheme LP-02 No No No No No No Yes No No No No No No Resolved Water has been accumulated over the Backfilled soil of raft. column steel bar also submerged in the water. Column steel bar is getting rusted due to work stopped for more than a month.
138 8360798 NARAINPUR GRAM PANCHAYAT WATER SUPPLY SCHEME LP-01 No No No No No Yes No No No No No No No
139 20089027 Saraichandrabhan urf Samaspur WATER SUPPLY SCHEME LP-07 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated inside the foundation of OHT. It may cause excessive settlement of soil below the foundation. Kindly complete piping work and do proper Backfilling immediately then construct an apron. Crack has observed in the plinth protection of the OHT.
140 20064973 Sarailalkhatoon urf Sheogarh Water Supply Scheme LP-08 No No No No No No Yes No No No No No No Resolved Cracks has been started developing in the 1st lift column of OHT. Kindly take corrective action regarding this issues.
141 20095009 BEDAULI TAPPA CHAURASI_ KHANPUR WATER SUPPLY SCHEME LP-407 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
142 20100315 BAGAHA_CHAUKI MAI ARAZAI PANASA UPERHAR WATER SUPPLY SCHEME LP-410 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
143 20086852 BARI WATER SUPPLY SCHEME LP-371 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
144 8362570 BASUPUR GRAM PANCHAYAT WATER SUPLY SCHEME LP-277 No No No No No No Yes No No No No No No Resolved The main bar spacing has been found 140 mm c/c however it should be 100 mm c/c as per drawing.
145 20023506 Anjana single village water supply scheme LP-217 Yes Yes No No No No No No Yes No No No No Resolved Resolved Resolved misAlignment of column of OHT is found. Honeycomb has been found in the columns and beams of Oht
146 20036740 Saraibirsingh single village water supply scheme LP-200 No No No No No No No No No No No No No
147 8360657 Ghamaha LP-41 No No No No No No No No No No No No No
148 20065759 Chakiya Girdh Kot Gram Panchayat Water Supply Scheme LP-57 No No No No No No No No No No No No No
149 20024816 Pach Deora Multi Village Water Supply Scheme LP-163 No No No No No No No No No No No No No
150 20097347 JOGAPUR WATER SUPPLY SCHEME 20097347/01 No No No No No No No No No No No No No
151 20023940 Sanraidasu urf Haripur village water supply scheme LP-521 No No No No No No No No No No No No No
152 8388576 Abhae Pur Gram Panchayat Water Suply Scheme LP-415 No No No No No No No No No No No No No
153 8388597 Sarai Todermal Urf Dandupur LP-245 No No No No No No No No No No No No No
154 8361124 Sari Patti Gram Panchayat Water Suply Scheme LP-258 No No No No No No No No No No No No No
155 20021043 Yaseenpur urf Karnayeepur LP-255 No No No No No No No No No No No No No
156 20017145 HARIRAM PATTI URF KATNAE MULTI VILLAGE WATER SUPPLY SCHEME LP-95 No No No No No No No No No No No No No
157 8361150 MURADPUR URF KHADIRPUR GRAM PANCHAYAT WATER SUPPLY SCHEME LP-367 No No No No No No No No No No No No No
158 20024814 Katiyahi hasanpur Korari Village Water Supply Scheme LP-314 No No No No No No No No No No No No No
159 20065869 Hasanpur Mai Chak Mansoor Water Supply Scheme LP-284 No No No No No No No No No No No No No
160 20088559 ATANPUR WATER SUPPLY SCHEME 20088559/01 No No No No No No No No No No No No No
161 20095070 MEERAKPUR_FAJLABAD URF KALOOPUR WATER SUPPLY SCHEME LP-243 No No No No No No No No No No No No No
162 20065210 Hasimpur Chabalapur Water Suppl scheme LP-394 No No No No No No No No No No No No No
163 20100386 BHIKHAMPUR MADWARA WATER SUPPLY SCHEME 20100386/01 No No No No No No No No No No No No No
164 20095061 KUSWAN_MARDANPUR WATER SUPPLY SCHEME 20095061/01 No No No No No No No No No No No No No
165 8360330 DHARI GRAM PANCHAYAT WATER SUPPLY SCHEME 8360330/01 No No No No No No No No No No No No No
166 20023965 kulmai Single Villaeg water supply scheme LP-280 No No No No No No No No No No No No No
167 20038822 Ikauni Single Village Water Supply Scheme LP-457 No No No No No No No No No No No No No
168 20023748 Akodha village water supply scheme LP-344 No No No No No No No No No No No No No
169 20024501 Hanthi Gani and Umari Ta Purva Multi Village Water Supply Scheme 20024501/01 No No No No No No No No No No No No No
170 20065894 bhabhikhar_gonthi water supply scheme LP-375 No No No No No No No No No No No No No
171 20077759 BARI BAJAHIYA WATER SUPPLY SCHEME LP-349 No No No No No No No No No No No No No
172 20085483 BARGOHANA KHURD WATER SUPPLY SCHEME LP-539 No No No No No No No No No No No No No
173 20095046 PURWA KHAS_CHHARIBANA WATER SUPPLY SCHEME LP-445 No No No No No No No No No No No No No
174 20038811 Ubhari Single Village Water Supply Scheme LP-442 No No No No No No No No No No No No No
175 20087132 MENARA WATER SUPPLY SCHEME 20087132/01 No No No No No No No No No No No No No
176 20100439 AKORA WATER SUPPLY SCHEME LP-449 No No No No No No No No No No No No No
177 20100435 PATTI NATH RAI WATER SUPPLY SCHEME 20100435/01 No No No No No No No No No No No No No
178 20017007 MADHOPUR SIYA DIH MULTI VILLAGE WATER SUPPLY SCHME LP-205 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.
179 20065756 Gobindpur Tawara Gram Panchayat Water Supply LP-188 No No No No No No Yes No No No No No No Resolved cracks have been observed on the top surface of precast slab of OHT. Cracks have been observed over the pedestal of oht.
180 20094983 BARASWAL_GADHWAKALA WATER SUPPLY SCHEME LP-355 No No No No No No Yes No No No No No No Resolved Water has been accumulated over the foundation of OHT. It may causes uneven settlement of foundation.
181 20023959 Balapur MVS water supply schemer LP-389 No No No No No Yes No No No No Yes No No Leakage has been occurred from the Zinc aluminium tank.
182 20097672 BASDAIYA WATER SUPPLY SCHEME LP-19 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the foundation of OHT. It may cause settlement of foundation.
183 20024060 Birsinghpur urf Alipur single village water supply scheme LP-47 No No No No No No Yes No No No No No No Resolved Water has been accumulated just beside the raft foundation. It may cause settlement of foundation.
184 20076845 BIGAHIYA WATER SUPPLY SCHEME LP-526 No No No No No No Yes No No No No No No Resolved Crack has been observed in the 1st braced beam of OHT.
185 20065452 Chaukatha tivariyan and Akhtariya multi village water supply scheme LP-131 No No No No No No Yes No No No No No No Resolved Rain water has been accumulated over the backfilled soil of OHT. Water will seepage inside the foundation and cause excessive settlement.