Agency-wise Major/critical Ncs at OHT

S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 20015920 SHIKARI CHAURA PWS 20015920/01 Yes No No No No No No No No No No No No Honeycombs found in second brace beam of oht, Finishing of column is not proper, Honeycombs obesrved at bottam of flat slab.
2 20030437 NEWARIYA PWS 20030437/01 Yes No No No No No No No No No No No No Honeycombing has been observed at multiple locations in the first brace beam. Poor finishing quality is noted in several columns and beams. Additionally, heavy rusting has been observed on the MS staircase of the OHT. Rectification should be done as per methodology provided by SWSM letter No: 2070/W-17(Sitapur)/2025-26/6531/Tech-16 dated:17/09/2025
3 20024393 BHITHAURA RAM SAHAY AND KALYANPUR PWS 20024393/01 Yes No No No No No No No No No No No No Honeycombing has been observed at the 1st brace of the OHT (Overhead Water Tank). This indicates improper compaction of concrete during casting, resulting in voids and exposed aggregates. Such defects can adversely affect the structural strength and long-term durability of the member. Proper repair and treatment are required to restore the integrity of the structure.
4 20024159 HUSAINPUR KHURUHRI 20024159/01 No No No No No Yes No No No No No No No 1. Leakage obervation in zinc- Alumn Tank.
5 20015701 DHARAMPUR PWS 20015701/01 No No No No No Yes No No No No No No No 1. Leakage observed at the bottom joint of the zinc-aluminium tank, near the base ring. 2. No water is being supplied from tank from 6 months instead of that direct water is being supplied.
6 20024502 Khaliput pur_ Satrahi PWS 20024502/01 No No No No No Yes No No No No No No No 1. Leakage obervation in zinc- Alumn Tank.
7 20056176 CHANDRKHA BUJURG PWS 20056176/01 No No No No No Yes No No No No No No No 1. Cracks have been observed at several locations in the grouting, indicating poor workmanship and inadequate compaction. 2. In addition, honeycombing has been observed in the pedestal beam, which indicates improper placement of concrete and insufficient vibration during concreting. 3. These deficiencies may adversely affect the structural strength and durability of the pedestal beam.
8 20034600 LALPUR MAHRI 20034600/01 No No No No No Yes No No No No No No No 1. Leakage observed at the bottom joint of the zinc-aluminium tank, near the base ring.
9 20015733 KATAR PWS 20015733/01 No No No No No Yes No No No No No No No 1. The precast Overhead Water Tank (OHT) work has been completed; however, leakage is observed in the tank, indicating possible defects in joints, sealing, or waterproofing. 2. Holes are observed in the support beams and braces, 3. These issues can affect the structural durability and serviceability of the OHT and require immediate inspection and necessary repair measures.
10 20015328 AKARA PWS 20015328/01 No No No No No Yes No No No No No No No 1. The precast overhead water tank structure work is completed; however, leakage has been observed in the zinc–aluminium water tank, indicating possible joint/seal failure.Holes are visible in each column and brace, which may affect structural durability and require immediate inspection and rectification. 2. Cracks have been observed in the grouting, which can lead to water seepage and reduction in structural strength.
11 20014946 AURAIYA TIKAI PWS 20014946/01 No No No No No Yes No No No No No No No 1. Grouting cracks have been observed at multiple locations. 2. These cracks indicate improper grouting and may lead to water seepage, reduction in bond strength, and long-term deterioration of the structure. 3. Immediate repair and re-grouting with suitable materials are required to prevent further damage and ensure structural durability.
12 20024537 Sachauli_Piprahawa ranjeetpur PWS 20024537/01 No No No No No Yes No No No No No No No 1. Plants growth has been observed around the Zincalume tank, indicating poor maintenance.Cracks have also been observed in the grouting at the joints of the precast elements of OHT, which may affect structural integrity and durability. 2. Rusting has been observed at staircase and ladder and bulging has been observed in zink alumn sheet.
13 20015335 BARDEHRA PWS 20015335/01 No No No No No Yes No No No No No No No 1. Water accumulation has been observed in the structure/site area. 2. Continuous water stagnation may reduce the soil bearing capacity and can create a safety hazard.The earthing of the lightning arrester is damaged/disconnected. 3. This may cause failure of the lightning protection system and can pose a serious risk to the structure and equipment during lightning strikes.
14 20024404 AKBARPUR 20024404/01 No No No No No Yes No No No No No No No 1. Plant growth has been observed in zink alumn tank, Rusting has been observed in staircase. 2. Water level indicator and Ladder was found damage.
15 20056173 EKDAGVA SV PWS 20056173/01 No No No No No Yes No No No No No No No 1. Hole has been observed in one of the braces of the OHT precast structure for transportation and Installation. 2. This may affect the structural strength and stability of the brace. 3.Immediate inspection and necessary repair are recommended to prevent further deterioration and ensure structural safety.
16 20024038 JAUGARH PWS 20024038/01 No No No No No Yes No No No No No No No 1. At jointing of hold down breckets nut bolting was found not fully tight with sheet, Seepage was found from bottom of oht surafce, 2. Safety net was found not fixed with slab at inlete and outlet of OHT.
17 20056004 ASANAHARIYA SV PWS 20056004/01 No No No No No No Yes No No No No No No 1. Water has been accumulating in the OHT campus for the past 6 months due to lack of soil backfilling inside the campus and absence of a proper drainage system. This prolonged waterlogging can weaken the soil, affect foundation stability, cause corrosion of metal componentS, damage concrete surfaces, and reduce the durability of the structure, even though all OHT works-includinB zinc-aluminium tank installation, Di piping, railings, and painting-have been completed.
18 20024552 KHAIRA KALA PWS 20024552/01 No No No No No No Yes No No No No No No 1. it was observed that the staircase erected does not comply with the technical specifications.
19 20055931 PRAHLADA_VISHUNAPUR MV PWS 20055931/01 No No No No No No Yes No No No No No No 1. The grouting of precast OHT slab has been developed multiple cracked leading of loss of watertightness, consequently active water seepage and dripping have been obesrvation on the underside of slab.
20 20016558 KAKANDHU PWS 20016558/01 No No No No No No Yes No No No No No No 1. The precast overhead tank work has been completed. 2. A hole/opening is observed at the first brace, which may affect structural integrity and requires proper sealing/rectification. 3. Cracks are observed in the plinth protection, indicating possible shrinkage, improper curing, or workmanship issues. 4. The painting work has been found spoiled, with poor surface finish, indicating inadequate surface preparation and substandard workmanship. Rectification and repainting are required as per specifications.
21 20024452 Ghorma Parsiya PWS 20024452/01 No No No No No No Yes No No No No No No 1. At several locations at the junction of the OHT slab support beam and column, pieces of gunny bag were found embedded in the concrete, indicating poor workmanship and improper shuttering practices. 2. In addition, honeycombing was observed in the 2nd brace, which indicates that the concrete was not properly compacted during casting. 3. These defects may adversely affect the structural strength and durability of the OHT.
22 20024454 Gujarwara_Rampur Kodari PWS 20024454/01 No No No No No No Yes No No No No No No 1. the plinth beam of the OHT, the steel reinforcement is visibly exposed, which indicates poor workmanship. 3. Due to exposure to moisture and environmental conditions, the reinforcement has started corroding. This may adversely affect the structural integrity.
23 20024556 Bagahi_Dakahi PWS 20024556/01 No No No No No No Yes No No No No No No 1. The staircase that has been insyis place abovythe second brace which has not been installed as per specification.ot was observed that plinth of OHT work is not started, 2. Zn-Al tank installation still pending.
24 20024237 BAIDAURA PWS 20024237/01 No No No No No Yes No No No No No No No Resolved 1. Leakage obervation in zinc- Alumn Tank. Letter no LTCD/WET/SWSM/2025-26/678 Dated: 14.01.2026 1. At jointing of hold down breckets nut bolting was found not fully tight with sheet, Seepage was found from bottom of oht surafce. 2. Safety net was found not fixed with slab at inlete and outlet of OHT. Letter no LTCD/WET/SWSM/2025-26/608 Dated: 06.08.2025
25 20055992 PIPRI MV PWS 20055992/01 No No No No No No Yes No No No No No No Resolved 1. Hold dowun bracket fixing not proper with slab in some place , nut bolting was found not fully tight in some place. LTCD/WET/SWSM/2025-26/609 Dated: 06.08-.2025
26 20024455 Kodri Digar_Kolabhr Majgawn PWS 20024455/01 No No No Yes No No No No No No No No No Resolved 1. The project was halted for long time and reinforcement bars have been corroded which may leads to structure durability & stability failures. LTCD/WET/SWSM/2025/596 Date: 16-Jul-2025
27 20030142 PARAS RAMPUR PWS 20030142/01 No No No Yes No No No No No No No No No Resolved 1. The project was halted for long time and reinforcement bars have been corroded which may leads to structure durability & stability failures. LTCD/WET/SWSM/2025/595 Date: 15-Jul-2025