| S.No. | Scheme ID | Scheme Name | OHT Code | Non-Compliance | Compliance(Current Status) | Description
|
||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Major Honey Comb | Alignment | Cube Test | Exposure | Deviation | Tank Observation | Other | SBC Issue | Demolish Partially | Demolish Fully | Under Examination | Serious Observation | Water Body | Compliance Major Honey Comb | Compliance Alignment | Compliance Cube Test | Compliance Exposure | Compliance Deviation | Compliance Tank | Compliance Other | Compliance SBC Issue | Compliance Demolish Partially | Compliance Demolish Fully | Compliance Under Examination | Compliance Serious Observation | Compliance Water Body | |||||
| 1 | 20087341 | MAHUWARI KHAS W/S SCHEME | 20087341/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | TPI Observation- Rusted steel was used during the raft casting works, which compromises the durability and structural integrity of the foundation and must be addressed immediately. | ||||||||||||
| 2 | 8359521 | DARAULI GRAM PANCHAYAT WATER SUPPLY SCHEME | 8359521/01 | No | No | No | No | No | No | No | Yes | No | No | No | No | No | Resolved | NABL Certified LAB SBC report had been submitted | ||||||||||||
| 3 | 20038941 | Sarahula W/S SCHEME | 20038941/01 | No | No | No | No | No | No | No | Yes | No | No | No | No | No | Resolved | NABL Certified LAB SBC report had been submitted | ||||||||||||
| 4 | 20082962 | KAITHWALI W/S SCHEME | No | No | No | No | No | No | No | Yes | No | No | No | No | No | Resolved | NABL Certified LAB SBC report had been submitted | |||||||||||||
| 5 | 20082962 | KAITHWALI W/S SCHEME | 20082962/01 | No | No | No | No | No | No | No | Yes | No | No | No | No | No | Resolved | NABL Certified LAB SBC report had been submitted | ||||||||||||
| 6 | 20017053 | SARAI SARIF W/S SCHEME | 20017053/01 | No | No | No | No | No | No | No | Yes | No | No | No | No | No | Resolved | NABL Certified LAB SBC report had been submitted | ||||||||||||
| 7 | 20082806 | SURHARPUR HARICHARAN W/S SCHEME | 20082806/01 | No | No | No | No | No | No | No | Yes | No | No | No | No | No | Resolved | NABL Certified LAB SBC report had been submitted | ||||||||||||
| 8 | 8362890 | ALIPUR BANGAWAN GRAM PANCHAYAT WATER SUPPLY SCHEME | 8362890/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | anti-rust chemical provided | ||||||||||||
| 9 | 20016953 | BASIPUR URF PIYARI_NINDOPUR W/S SCHEME | 20016953/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Anti-rust spray done by TKC | ||||||||||||
| 10 | 20017049 | RAMPUR PATARI W/S SCHEME | No | No | No | No | No | No | Yes | No | No | No | Yes | No | No | Resolved | Resolved | Sand Test Report Provided | ||||||||||||
| 11 | 20017018 | Kasera Pokhara W/S SCHEME | 20017018/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. Test Report Provided by TKC. | ||||||||||||
| 12 | 20058342 | Karmahari W/S SCHEME | 20058342/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Sand Test Report Provided By TKC. | ||||||||||||
| 13 | 8361270 | SISORA GRAM PANCHAYAT WATER SUPPLY SCHEME | 8361270/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Vibrator provided after instruction of TPIA. | ||||||||||||
| 14 | 20079186 | MAHADEWA W/S SCHEME (L&T) | 20079186/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | After instruction compliance done | ||||||||||||
| 15 | 20100580 | MIRANPUR SAKKA W/S SCHEME | 20100580/01 | No | No | No | Yes | No | No | Yes | No | No | No | No | No | No | Resolved | Resolved | 2. Panel Changed By TKC. 3. Panel changed By TKC 4. Leakage Rectified | |||||||||||
| 16 | 20017071 | RANJITPUR W/S SCHEME | 20017071/01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | Resolved | 1. Panel Changed By TKC. 2. Panel Changed By TKC. | ||||||||||||
| 17 | 20017003 | CHAUKIYA KHAS W/S SCHEME | 20017003/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. Anti-Rust Chemical coated by TKC | ||||||||||||
| 18 | 20097078 | BALASARI W/S SCHEME | 20097078/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | Observation- 1. During site inspection, it was observed that proper cover blocks were not used in the Overhead Tank (OHT) Raft reinforcement. The reinforcement bars were found resting directly on the shuttering or with inadequate/inconsistent cover, which is not incorrect. Rectified-.Cover Block Provided after instruction | |||||||||||||
| 19 | 20013797 | MUHAMMADPUR T CHAUDHARI AZMAL W/S SCHEME | 20013797/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. Dewatering Done after Instruction By TPIA | ||||||||||||
| 20 | 20016984 | SAURABH W/S SCHEME | 20016984/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. During the site inspection, rusted and corroded steel bars were observed to be used for the reinforcement of OHT (Overhead Tank) columns. 2. Stirrup spacing not maintain. 3. Tin sheet was used in place of steel foam work/wooden foam wok at the junction. Due to this, this steel sheet has penetrated into concrete and the size of the beam has also been reduced. Rectify Status- 1. Not Rectified 2. Stirrups Maintain after instruction given to TKC. 3. After instruction Proper shuttering used By TKC. | ||||||||||||
| 21 | 8361266 | DHARAWAN GRAM PANCHAYAT WATER SUPPLY SCHEME | 8361266/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation- 1. During site inspection, it was found that cover blocks were either missing, inadequately placed, or not aligned properly in both the floor slab and beam areas. This is a direct violation of standard construction practices and IS 456:2000 guidelines which 2. Rusted steel was used in the OHT slab casting reinforcement work works. This compromises the bonding between concrete and steel and poses a serious risk to structural integrity and durability. Rectification Status- Rectified 1. Cover block provided after instruction. 2. Anti-Rust Chemical photo provided. | ||||||||||||
| 22 | 20017049 | RAMPUR PATARI W/S SCHEME | 20017049/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation- 1. During the inspection of the OHT (Overhead Tank) column reinforcement work, it was critically observed that the proper binding of ring hooks at 135 degrees was not provided as per standard detailing requirements. Rectification Status- Rectified 1. Hooks provide of 135 degree after instruction. | ||||||||||||
| 23 | 20088976 | PAHARPUR KHURD & BHADAURA W/S SCHEME | 20088976/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation- 1. Rusted steel bars were used for the OHT reinforcement work. 2. Spacing of steel bar not as per drawing. Rectification Status- Rectified 1. Anti-rust Chemical Photo Provided. 2. Spacing rectified after instruction | ||||||||||||
| 24 | 20017024 | JOGA MUSAHIB W/S SCHEME | 20017024/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation- 1. During site inspection, it was observed that rusted and corroded steel bars were used for the reinforcement of the OHT pile column. Rectification Status- Rectified 1. Rectified by Welding of Column reinforcement. | ||||||||||||
| 25 | 8359522 | DEVAITHA GRAM PANCHAYAT WATER SUPPLY SCHEME | 8359522/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Observation- 1. OHT raft has been found submerged in water for a long time. 2. During site inspection, it was observed that the reinforcement steel used in the OHT raft column was in rusted condition. Rectification Status- Rectified Observation- 1. Dewatering done after instruction. 2. Not Rectified | |||||||||||||
| 26 | 20058440 | Aalapur W/S SCHEME | 20058440/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation- 1. During the site inspection pedestal steel found open and rusted...Repairing should as per methodology. Rectification Status- Rectified 1. Rectified By Grouting and injecting Method. | ||||||||||||
| 27 | 20088809 | BHAWAR KOL & LOCHIN W/S SCHEME | 20088809/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation- 1. It has been observed during site inspection that the reinforcement hooks were not bent to 135 degrees as per the standard specifications in multiple structural elements (e.g., columns, beams, pedestals). The deviation from the prescribed hook angle violation Rectification Status- Rectified 1. Hooks bent at 135 degree after instruction. | ||||||||||||
| 28 | 20017073 | SARAI GOKUL W/S SCHEME | 20017073/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation- 1. It has been observed during site inspection that the reinforcement hooks were not bent to 135 degrees as per the standard specifications in multiple structural elements (e.g., columns, beams, pedestals). The deviation from the prescribed hook angle violation. 2. Spacing of Slab Steel Bars Not as per Approved Drawing Rectification Status- Rectified 1. Hooks bent 135 degree after instruction. 2. After instruction spacing of Bar rectified. | ||||||||||||
| 29 | 20097115 | PACHARASI W/S SCHEME | 20097115/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation- 1. Leakage found in OHT DI jointing. Rectification Status- Rectified 1. Leakage Rectified and water is running now. | ||||||||||||
| 30 | 20058449 | Chandpur W/S SCHEME | 20058449/01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | Observation- 1. Undulation (wavy or uneven surface) has been observed on the OHT (Overhead Tank) column. This indicates poor workmanship or deviation during shuttering and concreting. Rectification Status- Not Rectified | |||||||||||||
| 31 | 20017026 | TARAW W/S SCHEME | 20017026/01 | No | No | No | No | Yes | No | Yes | No | No | No | No | No | No | Resolved | Resolved | Observation- 1. Rusted steel was used in the OHT Raft column casting works. This compromises the bonding between concrete and steel and poses a serious risk to structural integrity and durability. 2. The Plain Cement Concrete (PCC) layer has disintegrated, with loose and unbound aggregates, indicating a serious quality failure in material mixing, placement, or curing. This compromises the structural base meant to uniformly distribute loads and support. 3. The hooks of reinforcement bars in the pedestal are not bent at 135° as per standard specifications. Instead, they appear to be either straight or bent at a lesser angle. 4. The bottom cover provided is only 25mm instead of the required 50mm as per structural specifications. Additionally, bricks are being used as cover blocks, which is an unacceptable practice. 5. During inspection, it was observed that the steel reinforcement in the raft foundation is not maintained at a uniform level, which is not as per structural and construction standards. This level variation can lead to improper concrete cover, misalignment. Rectification Status- Rectified 1. Rectified(Photo related to anti rust provided by TKC 2. Rectified by Finishing. 3. Bar Bent at 135 degree after instruction. 4. Cover changed after instruction. 5. Unformity of raft is maintained during casting of raft by Concrete. | |||||||||||
| 32 | 20088804 | KAROYI W/S SCHEME | 20088804/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation- 2. Rusted steel was used in the OHT Raft foundation casting works. This compromises the bonding between concrete and steel and poses a serious risk to structural integrity and durability. Rectification Status- Rectified 1. Anti-Rust Chemical Provided. | ||||||||||||
| 33 | 8359514 | ARILLA GRAM PANCHAYAT WATER SUPPLY SCHEME | 8359514/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation: 1. OHT Plint protection has been found crack at many places. Corrective Action taken: Rectification has been done as per approved methodology. | ||||||||||||
| 34 | 20097744 | CHAK MAHATAB W/S SCHEME | 20097744/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation: 1. Proper bending of OHT column ring hook at 135 degree was not provided Corrective Action taken: OHT Column Rings hook has been bend at 135 degree as per IS code/as per drawing. | ||||||||||||
| 35 | 20092075 | ASAICHANDPUR W/S SCHEME | 20092075/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observation: OHT raft found steel rusted. Corrective Action taken: Rust removed by sand paper & rust removal Paint. | ||||||||||||
| 36 | 20088799 | JAMEEN MUNDRABHA W/S SCHEME | 20088799/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | Observation- Proper Dressing with Compaction is required in OHT Excavation for PCC work. | |||||||||||||
| 37 | 20100569 | MALIKPURA W/S SCHEME | 20100569/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||
| 38 | 20100583 | GOPALPUR W/S SCHEME | 20100583/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||
| 39 | 8361268 | KUSUMHI KALAN GRAM PANCHAYAT WATER SUPPLY SCHEMEH | 8361268/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||
| 40 | 20100574 | MADHUBAN MU. YUSUFPUR W/S SCHEME | 20100574/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||
| 41 | 20017197 | Rampur Jiwan W/S SCHEME | 20017197/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||
| 42 | 20082944 | MANIHARI KHAS W/S SCHEME | 20082944/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||
| 43 | 20098513 | SAHABPUR W/S SCHEME | 20098513/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||
| 44 | 20088597 | MATUK PUR W/S SCHEME | 20088597/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||
| 45 | 20017037 | MUSTAFABAD W/S SCHEME | 20017037/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||