Agency-wise Major/critical Ncs at OHT

S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 20015352 Bhartauk Water Supply Scheme 20015352/01 Yes No No Yes Yes No No No No No No No No Resolved Resolved Resolved Bottom dowel bars of connecting beam for staircase column are not provided
2 20020277 BHOJIPURA water supply scheme 20020277/01 No No No No Yes No No No Yes No No No No Resolved Resolved 1. OHT slab walkway width found at site that 1000mm one side from the RB2 but as per approved drawing it should be one side 415mm and other side 585mm from the centre of RB2. Dismantle it and recast OHT slab walkway as per approved drawings. 2. Two different sizes of OHT precast steps used at site due to which the gap between two steps of stair find different at different-different position. Rectify immediately and provide size of OHT precast steps as per approved drawings.
3 20089008 Richhola Kifaytullah water supply scheme 20089008/01 No No No No No No Yes No Yes No No No No Resolved Resolved Casting of 2nd lift columns above TB-03 has been done approximately four months ago, but de-shuttering of columns not done so far, curing of columns not done.
4 20020456 BHEEKAMPUR & DHEERPUR water supply scheme 20020456/01 No No No No Yes No Yes No No No No No No Resolved Resolved Development length of Bars in RB-01 found 700mm for 20mm bar in place of '1000mm, 500mm for 16mm bar in place of 800mm and Laps not done staggered. 2. Number of extra bars and cutting length of extra bars in RB-01 not found as per approved drawing. 3. Hooks of stirrups for ring beam were not bending; it should be bend as per specification. 4. Vertical bars of columns not found Ld+SD at junction point of RB-01. 5. Cutting length of bottom distribution Bars not found as per drawing. 6. Reinforcements for TB-04 and walkway not provided as per approved drawing. 7. Provide more vertical support from TB-2 to TB-3 and center portion of slab. 8. Main bars and extra bars for all TB-03 for staircase not provided as per approved drawing.
5 20013215 MANPUR AHAIYAPUR Water Supply Scheme 20013215/01 Yes Yes No No No No No No Yes No No No No Resolved Resolved Resolved Columns above ground level and TB-01 are having clear honeycombing and mis-alignment up to TB-01.
6 20015626 Antapur water supply scheme 20015626/01 No No No No No Yes No No No No No No No Resolved Leakage found in zinc-alum tank around the jointing of sheets in bottom.
7 20034979 Atangaogi & Masiwali Nagar 20034979/01 No No No No No No Yes No No No No No No Resolved Casting of staircase without checking & information
8 20013192 Saidoopur Lashkariganj Water Supply Scheme 20013192/01 No No No No Yes No Yes No No No No No No Resolved Resolved OHT staircase constructed not as per drawing/design.
9 8359750 SARAI TALFI MUSTQIL 8359750/01 No No No No Yes No Yes No No No No No No Resolved Resolved OHT staircase constructed not as per drawing/design.
10 20020573 ASPUR HASAN ALI water supply scheme 20020573/01 Yes No No Yes No No No No Yes No No No No Resolved Resolved Resolved Current Status -Dismantled all Column/Rectification done
11 20038443 Sadullaganj 20038443/01 No No No No Yes No No No Yes No No No No Resolved Resolved Resolved Resolved Resolved Resolved cracks have developed in the MLB associated with the staircase and constructed staircase does not align with the approved drawings, specific deviations in dimensions, alignment .
12 20091912 Shivnagar Naugawan water supply scheme 20091912/01 No No No No Yes No No No Yes No No No No Resolved Resolved riser and tread dimensions of the constructed staircase do not conform to the approved design/drawing specifications.
13 20038424 Deoria Jagir & Gupalapur 20038424/01 No No No No Yes No No No No No No No Yes Description of NC- 1. Dowels for MLB-01 for staircase were not at proper location and level as per approved drawing. 2. Exposed column reinforcements were rusted. 3.Surface of tie beams having nos. of pin holes. Suggested Rectification- Contractor is instructed to submit a detailed rectification plan and methodology Current Status- Rectification Work In Progress
14 20058403 Mawai & Mundia Chetram Water Supply Scheme 20058403/01 No No No No Yes No No No No No No Yes No Description of NC- The center-to-center distance between columns for the construction of OHT below ground level differ from the approved drawing. Suggested Rectification- Contractor is instructed to dismantled and reconstruct. Current Status- Rectification Work In Progress
15 20053664 Khajuria 20053664/01 No Yes No No No No No No Yes No No No No Description of NC- Honey combing & Misalignment in OHT Columns, columns casted without RFI and also OHT slab casted without information to TPIA/UPJN, even though contractor engineer also not available during casting work and cubes also not casted. Suggested Rectification- demolish & Reconstruct after corrosion treatment of Reinforcement steel exposed for long. Current Status- Rectification Work In Progress
16 20034976 Noorpur & Ghunsi 20034976/01 No No No No No No No No Yes No No Yes No Description of NC- Soffit of slab found having undulations and cracks near columns and ring beam junction. Suggested Rectification-demolish & Reconstruct after corrosion treatment of Reinforecement steel exposed for long. Current Status- Rectification Work In Progress