S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 20063288 Amatamau & Rausinghpur Water Supply Scheme 20063288/01 No No No No Yes No No No No No No No No
2 20097237 BAHERA JJM SCHEME 20097237/01 Yes No No No No No Yes No No No No No No During inspection, the OHT structure was found to be in "poor condition," showing signs of potential honeycombing, cracks, or inadequate concrete strength.
3 20097554 BAHORANPUR JJM SCHEME 20097554/01 No Yes No Yes No No Yes No No No No No No Wooden pieces embedded between OHT Column and Tie beam junction.
4 20064808 Barhaiya & Narni Water Supply Scheme 20064808/01 No Yes No No Yes No No No No No No No No
5 20016529 Dhakiya 20016529/01 Yes Yes No Yes No No No No No No No No No
6 20099533 Jalalpur Water Supply Scheme 20099533/01 No No No Yes Yes No No No No No No No No
7 20016437 LALPUR 20016437/01 No Yes No No No No No No No No No No No
8 20058199 Mirzapur 20058199/01 Yes Yes No No No No No No No No No No No
9 20019545 Mohammadpur Kala 20019545/01 No Yes No No No No Yes No No No No No No Visible structural crack seen in staircase at the column junction, indicating potential weakness
10 20099980 MOHARAVA JJM SCHEME 20099980/01 No No No No No No Yes No No No No No Yes Water logging has been observed on the OHT raft, which may adversely affect the durability and strength of the raft foundation if not addressed.
11 20084373 REWAN WATER SUPPLY SCHEME 20084373/01 No Yes No No Yes No Yes No No No No No No 1-The bend pipes have been installed in the vertical pipeline, which is not permitted. The pipe should be installed in a straight vertical alignment. The existing bend arrangement may cause water pressure and flow issues. 2-Gaps have been observed around the pipe penetration in the OHT slab, which is not acceptable. This may lead to leakage and deterioration of the slab.
12 20011890 RUSTAM NAGAR 20011890/01 No Yes No No No No No No No No No No No
13 20016440 Seharu Khera 20016440/01 Yes No No Yes No No No No No No No No No
14 20019570 SUKAIPUR 20019570/01 No Yes No No Yes No Yes No No No No No No 1-Visible structural crack seen in OHT walkway slab top surface & staircase last flight bottom surface area, indicating potential weakness. 2-OHT painting work has not been carried out properly. Uneven paint application and poor surface finish have been observed at various locations. 3-The bend pipes have been installed in the vertical pipeline, which is not permitted. The pipe should be installed in a straight vertical alignment. The existing bend arrangement may cause water pressure and flow issues.
15 20099950 SUREPARA & DATOONI JJM SCHEME 20099950/01 No No No Yes No No No No No No No No No
16 20066216 Urdauli Water Supply Scheme 20066216/01 Yes No No Yes No No Yes No No No No No No Water logging has been observed on the OHT raft, which may adversely affect the durability and strength of the raft foundation if not addressed
17 20019538 Anogi 20019538/01 No No No No Yes No No No No No No No No
18 20058411 Bahlol Nagar 20058411/01 No Yes No No Yes No No No No No No No No
19 20065163 Banehra Birbal & Bhethra Madho Water Supply Scheme 20065163/01 No Yes No No No No Yes No No No No No No Visible structural crack seen in staircase above 1st brace beam at the column junction, indicating potential weakness.
20 20097354 AKHATYARPUR JJM SCHEME 20097354/01 Yes No No Yes Yes No No No No No No No No
21 20098440 BARKHERIA JJM SCHEME 20098440/01 No Yes No No No No No No No No No No No
22 20019558 Barwi Baruwa 20019558/01 Yes Yes No Yes No No No No No No No No No
23 20063292 Chaupariya & Fattepur Multi Village Scheme 20063292/01 Yes No No No No No No No No No No No No
24 20016453 MIRZAPUR DAXINI 20016453/01 No Yes No No No No No No No Yes No No No OHT remains unsafe even after third-party (IIT) evaluation and is not fit for service.
25 20099958 CHANDAULI JJM SCHEME 20099958/01 No Yes No No No No No No No Yes No No No OHT remains unsafe even after third-party (IIT) evaluation and is not fit for service.
26 20098427 THANAPATTI JJM SCHEME 20098427/01 No Yes No No No No No No No Yes No No No OHT remains unsafe even after third-party (IIT) evaluation and is not fit for service.
27 20065918 Ladilapur 20065918/01 Yes No No Yes No No No No No Yes No No No OHT structure is unsatisfactory based on UPV results.