| S.No. | Scheme ID | Scheme Name | OHT Code | Non-Compliance | Compliance(Current Status) | Description
|
||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Major Honey Comb | Alignment | Cube Test | Exposure | Deviation | Tank Observation | Other | SBC Issue | Demolish Partially | Demolish Fully | Under Examination | Serious Observation | Water Body | Compliance Major Honey Comb | Compliance Alignment | Compliance Cube Test | Compliance Exposure | Compliance Deviation | Compliance Tank | Compliance Other | Compliance SBC Issue | Compliance Demolish Partially | Compliance Demolish Fully | Compliance Under Examination | Compliance Serious Observation | Compliance Water Body | |||||
| 1 | 20012442 | Bhuwalpur Sisni GP Water Supply Scheme | 20012442/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Lap provided in non-lapping Zone | |||||||||||||
| 2 | 20085623 | Gora Ubarani Water Supply Scheme | 20085623/01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | One or more RCC columns appear not vertically plumb when observed from the side angle | |||||||||||||
| 3 | 20090886 | Kathgar Water Supply Scheme | 20090886-OHT-01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | lt has been observed that the column above 3rd brace beams have undergone extensive repairs and are misaligned. | |||||||||||||
| 4 | 20012772 | Jariya GP Water Supply Scheme | 20012772-OHT-01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | lt has been observed through visual inspection that the one column above 1st and 2nd brace beams are misaligned, | |||||||||||||
| 5 | 20062178 | JAHANPUR KODAR WATER SUPPLY SCHEME | 20062178-OHT-01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | lt has been observed through visual inspection that the one column above 1st and 2nd brace beams are misaligned, | |||||||||||||
| 6 | 20090255 | BEWAL WATER SUPPLY | 20090255/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in the OHT slab, ring beam, and walkway | |||||||||||||
| 7 | 20062207 | JHARAHA WATER SUPPLY SCHEME | 20062207/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing have been observed in one OHT column above the raft. | |||||||||||||
| 8 | 20090029 | Kamalpur Water Supply Scheme | 20090029/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in the OHT walkway and ring beam. | |||||||||||||
| 9 | 20022721 | Ekauni GP Water Supply Scheme | 20022721/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Exposed reinforcement bars have been observed in the structure staircase of the Overhead Tank. | |||||||||||||
| 10 | 20092516 | Purasi Water Supply Scheme | 20092516/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in the OHT beam & Column and Reinforcement exposed in Tie Beam. | |||||||||||||
| 11 | 8362286 | HIDAIN | 8362286/01 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Leakage has been observed in the Zinc-Alum tanks, leading to water leaking/seeping out and stagnating around the tank base. | |||||||||||||
| 12 | 20094592 | Lakhanpur Water Supply Scheme | 20094592-OHT-01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | From visual inspection, the column appears to be misaligned. The change in its profile and the eccentricity near the beam connection suggest that the column may not be perfectly vertical or centered. | |||||||||||||
| 13 | 8362499 | SULTANPUR | 8362499/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in the Slab beam & Column and Reinforcement exposed in Beam & Slab. | |||||||||||||
| 14 | 20090875 | SAWANPUR NEWADA Water Supply Scheme | 20090875-OHT-01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | From visual inspection, the column appears to be misaligned. The change in its profile and the eccentricity near the beam connection suggest that the column may not be perfectly vertical or centered. | |||||||||||||
| 15 | 8362069 | JARIYARI | 8362069-OHT-01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | From visual inspection, the column appears to be misaligned. The change in its profile and the eccentricity near the beam connection suggest that the column may not be perfectly vertical and Honeycombing also found in Ring beam and Column." | |||||||||||||
| 16 | 20017220 | Baitu GP Water Supply Scheme | 20017220-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant Honeycombing with exposed reinforcement bars have been observed in the Slab,Ring Beam and staircase of the Overhead Tank. | |||||||||||||
| 17 | 20062140 | BADAWAR WATER SUPPLY SCHEME | 20062140-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant Honeycombing with exposed reinforcement bars have been observed in the Overhead Tank. | |||||||||||||
| 18 | 20014907 | Maha Khera GP Water Supply Scheme | 20014907/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | At the bottom of the 1st and 2nd tie beams near the column junction, steel reinforcement is found exposed and honeycombing is observed. | |||||||||||||
| 19 | 20064084 | Baghai Ahalwar WATER SUPPLY SCHEME | 20064084-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in the OHT Stair, beam & Column and Reinforcement exposed in Stair and Proper finishing not obtained between OHT Column and Tie beam junction. | |||||||||||||
| 20 | 8362192 | BAGHAIL | 8362192-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in the OHT beam & Column. | |||||||||||||
| 21 | 20090251 | BARARA BUJURG Water Supply Scheme | 20090251-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in the OHT beam & Column | |||||||||||||
| 22 | 8360916 | Jagjiwanpur Amariya | 8360916/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Honeycombing has been observed in the OHT beam and columns. The repair work carried out at the beam-column junctions has been found to be improperand inadequate. | |||||||||||||
| 23 | 8362130 | BAHUDA KHURD | 8362130/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant Honeycombing with exposed reinforcement bars have been observed in the Slab,Ring Beam and staircase of the Overhead Tank. | |||||||||||||
| 24 | 20012294 | Kumbhi GP Water Supply Scheme | 20012294-OHT-01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Exposed reinforcement bars have been observed in the Ring beam structure of the Overhead Tank | |||||||||||||
| 25 | 20012584 | Pindauli GP Water supply Scheme | 20012584/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Exposed reinforcement bars have been observed in the Ring beam structure of the Overhead Tank (OHT) | |||||||||||||
| 26 | 20087184 | Surasana Water Supply Scheme | 20087184-OHT-01 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Leakage has been observed in the Zinc-Alum tanks, leading to water leaking/seeping out and stagnating around the tank base. | |||||||||||||
| 27 | 20011312 | Manehroo GP Water Supply Scheme | 20011312-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in slab Ring beam, column below slab and TB3 and Reinforcement found exposed. | |||||||||||||
| 28 | 8360623 | Padri Ganeshpur | 8360623-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | TB1 was found with honeycombing and reinforcement bars are exposed and OHT slab ring beam surface also shows honeycombing. | |||||||||||||
| 29 | 8362109 | PAHARPUR KAHSO | 8362109-OHT-01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | Column above TB2 and TB3 appears to be misaligned from visual inspection. | |||||||||||||
| 30 | 8360622 | Chandwal | 8360622-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | "Significant Honeycombing was observed in the slab ,TB1 and TB2 and Reinforcement was found exposed in beam juction at TBI" | |||||||||||||
| 31 | 20064090 | Khanuwa WATER SUPPLY SCHEME | 20064090/01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | It was observed that 02 columns appear to be misaligned from the intended alignment. Futhermore, improper linishing was observed at the colurnn-beam junction. | |||||||||||||
| 32 | 20012459 | Rampur Kasiha GP Water Supply Scheme | 20012459/01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | From visual inspection, the column appears to be misaligned. | |||||||||||||
| 33 | 8362389 | KUNDAULI | 8362389-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in slab Ring beam. | |||||||||||||
| 34 | 20066102 | Sarai Dugosha Water Supply Scheme | 20066102-OHT-01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Significant honeycombing has been observed in slab Ring beam and and Finishing is not proper at junction of TB1. | |||||||||||||
| 35 | 20013146 | Bisaiyya GP Water Supply Scheme | 20013146/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Reinforcenrent bars were found exposed at TB2 and Finishing is not proper at junction of Beams. Also cracks observed at staircase of OHT. | |||||||||||||
| 36 | 8362090 | SARAIDAMU | 8362090-OHT-01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | From visual inspection 2 columns appear to be misaligned from the intended alignment. Furthermore, improper finishing was observed at the column-beam junction. | |||||||||||||