| S.No. | Scheme ID | Scheme Name | OHT Code | Non-Compliance | Compliance(Current Status) | Description
|
||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Major Honey Comb | Alignment | Cube Test | Exposure | Deviation | Tank Observation | Other | SBC Issue | Demolish Partially | Demolish Fully | Under Examination | Serious Observation | Water Body | Compliance Major Honey Comb | Compliance Alignment | Compliance Cube Test | Compliance Exposure | Compliance Deviation | Compliance Tank | Compliance Other | Compliance SBC Issue | Compliance Demolish Partially | Compliance Demolish Fully | Compliance Under Examination | Compliance Serious Observation | Compliance Water Body | |||||
| 1 | 20014105 | KHUTENA PAYAGPUR PWS | 20014105/01 | Yes | No | No | No | No | No | Yes | No | No | No | No | No | No | *Improper overlapping of rebars. *Incorrect placement of chair bars. *Inadequate anchoring of bars and required adjustments in the formwork. *Major honeycombing observed in beams and pile cap due to improper use of shuttering & poor quality execution | |||||||||||||
| 2 | 20016148 | SAUGAHANA PHAKHARPUR PWS | 20016148/01 | No | Yes | No | No | Yes | No | Yes | No | No | No | No | No | No | *The OHT has not been constructed with proper vertical alignment. *Budling and misalignment at Junction point. *The overall quality of workmanship appears to be below acceptable standards, with visible seams and other inconsistencies. | |||||||||||||
| 3 | 20072319 | SEMARI GHATHI MIHIPURWA PWS | 20072319/01 | Yes | Yes | No | No | Yes | No | Yes | No | No | No | No | No | No | *Honeycombing was found on the column surfaces, which indicates improper compaction and poor workmanship. *Longitudinal reinforcement has not been placed as per the design specifications. *Junction boxes were not provided during the pouring of concrete at column brace. | |||||||||||||
| 4 | 20018878 | CHAUGOI BILASPUR NAWABGANJ PWS | 20018878/01 | Yes | No | No | Yes | No | No | No | No | No | No | No | No | No | *Major honeycomb observed at the column brace junction as well as in the staircase. *Reinforcement in the OHT staircase is exposed after casting of Staircase, indicating poor workmanship. | |||||||||||||
| 5 | 20020346 | SAMBHU TEKRI PAYAGPUR PWS | 20020346/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Steel is cut from the column at GL level. | |||||||||||||
| 6 | 20072325 | KATGHAR MIHIPURWA PWS | 20072325/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Reinforcement bars at the site have been found cut/chopped by unknown persons/villagers. | |||||||||||||
| 7 | 20016167 | KHANPUR MALLOH VISESHWARGANJ PWS | 20016167/01 | No | No | No | No | Yes | No | Yes | No | No | No | No | No | No | *Improper shuttering is used; improper finishing is observed. *Edge and corners of steps is improper, poor finishing seams in staircase. | |||||||||||||
| 8 | 20013703 | NARAYANPUR PAYAGPUR PWS | 20013703/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Few vertical column steels chopped at GL level. | |||||||||||||
| 9 | 20072326 | SUJAULI MIHIPURWA PWS | 20072326/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Few vertical column steel chopped at GL level . | |||||||||||||
| 10 | 20016654 | KANDAUSA FHAKHARPUR PWS | 20016654/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Few vertical column steels chopped at GL level . | |||||||||||||
| 11 | 20051979 | NATHUWAPUR MAHASI PWS | 20051979/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *Staircase dimension error riser and thread is not found as required or as per approved drawing. | |||||||||||||
| 12 | 20018877 | BANKURI NAWABGANJ PWS | 20018877/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Few vertical column steel chopped at GL level. | |||||||||||||
| 13 | 20072218 | KHANPUR HUZOORPUR PWS | 20072218/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Few vertical columns steel chopped at GL level . | |||||||||||||
| 14 | 20020332 | HATWA HARDAS PAYAGPUR MVS PWS | 20020332/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *3rd lift staircase few steps dimension is not as per approved drawing deviation seams in dimension of thread and riser. | |||||||||||||
| 15 | 8362923 | SIRAULA GRAM PANCHAYAT RURAL DRINKING WATER SUPPLY SCHEME | 8362923/01 | Yes | Yes | No | No | No | No | No | No | No | No | No | No | No | *Honeycomb seams in brace beam of OHT. *alignment issues and finishing issues in staircase. | |||||||||||||
| 16 | 20016089 | JUDA SHIVPUR PWS | 20016089/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *Dimensional error in staircase. | |||||||||||||
| 17 | 20048313 | JUMERPUR JARWAL MVS PWS | 20048313/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | *Honeycomb at OHT column. | |||||||||||||
| 18 | 20059445 | KATGHARA KALA HUZOORPUR MVS PWS | 20059445/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *Dimensional error in staircase of OHT. | |||||||||||||
| 19 | 20016202 | NEJABHAR VISESHWARGANJ PWS | 20016202/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Few vertical columns steel chopped at GL level . | |||||||||||||
| 20 | 20018638 | NARAUNDA JARWAL PWS | 20018638/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *Poor workman ship seams in the construction of OHT at staircase, air voids and improper finishing seams. | |||||||||||||
| 21 | 20072262 | SANTHA KAISARGANJ PWS | 20072262/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Few vertical columns steel chopped at GL level . | |||||||||||||
| 22 | 20014710 | ALI NAGAR KHURD RISIYA MVS PWS | 20014710/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *Air voids and honeycomb in bottom ring beam of OHT. | |||||||||||||
| 23 | 20017524 | CHARDAHA CHANDAN CHITTAURA PWS | 20017524/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Reinforcement at GL is deformed. | |||||||||||||
| 24 | 20020240 | DIGIT PURWA VISESHWARGANJ PWS | 20020240/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Column reinforcement chopped from GL level of OHT. | |||||||||||||
| 25 | 20034898 | GANGA JUMNI GRAM PANCHAYAT WATER SCHEME | 20034898/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Reinforcement bars of column is chopped at GL level. | |||||||||||||
| 26 | 20034885 | DALJIT PURWA GRAM PANCHAYAT WATER SCHEME | 20034885/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Vertical column reinforcement is cut from GL level. | |||||||||||||
| 27 | 20014113 | SEMRIYAWAN PAYAGPUR PWS | 20014113/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *The brace beam dimensions of the 2nd brace were measured and found to be 20-30 mm more than the dimensions specified in the approved drawings. | |||||||||||||
| 28 | 20011160 | RAMWAPUR HUZOORPUR MVS PWS | BAH/PNC/B8/38 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *OHt lightning arrestor Strip is not as provided as required, insulation of strip is not done properly. | |||||||||||||
| 29 | 20072386 | RAMPUR BARAIE RISIA PWS | 20072386/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *OHT vertical column steel is chopped from GL level . | |||||||||||||
| 30 | 20034869 | ARAI KALA GRAM PANCHAYAT WATER SCHEME | 20034869/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | *Honeycomb is observed in 1st brace beam, at few places air voids observed. | |||||||||||||
| 31 | 20013696 | KAANDH BHARI VISESHWARGANJ PWS | 20013696/01 | Yes | Yes | No | No | No | No | No | No | No | No | No | No | No | *Minor honeycomb in 3rd brace beam. * Verticality issue in column. | |||||||||||||
| 32 | 8362941 | RAY DEEH GRAM PANCHAYAT RURAL DRINKING WATER SUPPLY SCHEME | 8362941/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | *Honeycomb in staircase 7th lift. | |||||||||||||
| 33 | 20016690 | SALARPUR KAISARGANJ MVS PWS | 20016690/01 | Yes | No | No | No | Yes | No | No | No | No | No | No | No | No | *honeycomb and reinforcement issue in OHt bottom dome. * staircase waist slab thickness is not as per approved drawing . | |||||||||||||
| 34 | 20039628 | BASANTPUR HUZOORPUR PWS | 20039628/01 | Yes | No | No | No | Yes | No | No | No | No | No | No | No | No | *honeycomb in OHt bottom dome staircase waist slab . *stair caser work is not done as approved drawing. | |||||||||||||
| 35 | 20016681 | KHAJURA VISESHWARGANJ PWS | 20016681/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | *honeycomb is observed in bottom dome and balcony. | |||||||||||||
| 36 | 20048334 | PEDWA JARWAL MVS PWS | 20048334/01 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | *Deviation in zinc alum erection work at OHT. | |||||||||||||
| 37 | 20013896 | PIPRIYA BADARKA PWS SVS | 20013896/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | *honeycomb is observed in OHT pile cap . | |||||||||||||
| 38 | 20069803 | MAKRANDPUR MAHIS PWS | 20069803/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *Regarding poor workmanship, column starter constructed in ir regular shape. | |||||||||||||
| 39 | 20039633 | PARSOHAR JARWAL PWS | 20039633/01 | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | *Regarding poor finishing of OHT column. *Honeycomb in bottom dome. *Reinforcement steel found exposed. | |||||||||||||
| 40 | 20034904 | KAILASHPUR JHOMAN GAON GRAM PANCHAYAT WATER SCHEME | 20034904/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *Deviation from drawing in staircase thread and riser. | |||||||||||||
| 41 | 20014081 | CHAUDHARI GAON MIHIPURWA PWS | 20014081/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Leakage and seepage are observed in bottom dome and cylindrical wall. | |||||||||||||
| 42 | 20016095 | USARA JARWAL PWS | 20016095/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Honeycombing is observed in the cylindrical wall of the OHT, with visible voids and stone pockets, indicating poor compaction and inadequate concrete consolidation. | |||||||||||||
| 43 | 20031358 | GODANI BASAHI CHITTAURA PWS | 20031358/01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | Resolved | *Miss alignment in 1st lift column above 1st brace. | ||||||||||||
| 44 | 20077191 | LALPUR CHANDJHAR & GOPIA MIHIPURWA MVS PWS | 20077191/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Cantilever beam reinforcement is chopped from column. | ||||||||||||
| 45 | 20048286 | ATHAISHA JARWAL MVS PWS | 20048286/01 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | *28 DAYS 2nd Lift column above 1st brace beam cube fail. | ||||||||||||
| 46 | 20016108 | KALWARI NAWABGANJ PWS | 20016108/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Few vertical columns steel chopped at GL level . | ||||||||||||
| 47 | 20013702 | KHAJURI PAYAGPUR PWS | 20013702/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | *Staircase steel exposed form several months rusting issue. | ||||||||||||