Agency-wise Major/critical Ncs at OHT

S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 20059187 Khanpur Urf Birbhanpur WATER SUPPLY SCHEME 20059187/01 No Yes No No No No No No No No No No No The alignment of one column was not found in plumb.
2 20070441 DARIGAPUR WATER SUPPLY Merge SCHEME 20070441/01 Yes No No No No No No No No No No No No Significant honeycombing has been found on the OHT structure
3 20078815 BAIRAMPUR WATER SUPPLY MERGE SCHEME 20078815/01 No Yes No No No No No No No No No No No lt has been observed that the column above 1st brace beams have undergone extensive repairs and are misaligned.
4 20069346 ONAIY JANGAL WATER SUPPLY SCHEME 20069346/01 No Yes No No No No No No No No No No No lt has been observed that the column above 1't brace beams have undergone extensive repairs and are misaligned.
5 20059703 RAJAPUR CHAK BIBI WATER SUPPLY SCHEME 20059703/01 Yes No No No No No No No No No No No No Significant honeycombing has been observed in the OHT Column and Cracks were found in the column, and it appears to have been repaired. Additionally, the column size does not match the dimensions shown in the drawing.
6 20065908 THULWASA Water Supply Scheme 20065908/01 Yes No No No No No No No No No No No No Significant honeycombing has been observed in the OHT Beam & Stair.
7 20067268 SEWALPUR WATER SUPPLY SCHEME 20067268/01 Yes No No No No No No No No No No No No Steel reinforcement is exposed at the bottom of the OHT 3rd brace beam, and honeycombing is also observed in the concrete, which may affect durability and structural performance.
8 20065980 HARDI Water Supply Scheme 20065980/01 No No No No No No Yes No No No No No No Due to prolonged stoppage of work and the presence of a nearby high-tension electrical line, rusting has been observed on the reinforcement of the OHT columns. This condition poses both quality and safety concerns
9 20078774 KRISHNAPUR TALA WATER SUPPLY SCHEME 20078774/01 No Yes No No No No No No No No No No No From visual inspection,2 nos of columns appears to be misaligned.
10 20069484 KEWALPUR MAFI WATER SUPPLY MERGE SCHEME 20069484/01 No Yes No No No No No No No No No No No From visual inspection, the column appears to be misaligned. The change in its profile and the eccentricity near the beam connection suggest that the column may not be perfectly vertical or centered.
11 20074530 GODWARA Water Supply Scheme 20074530/01 No No No No No Yes No No No No No No No Leakage was observed on the Zn-Al tank, and seepage was also noticed on the slab of the Overhead Tank.
12 20067405 JASUALI WATER SUPPLY SCHEME 20067405/01 No No No Yes No No No No No No No No No Reinforcement bars are exposed in slab and slab beam.