Agency-wise Major/critical Ncs at OHT

S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 8152383 Dhawarra GOV OHT / 023 /DHUDHAIYA Yes Yes No No No No Yes No No No No No No 1. Major honeycombing has been observed in 1st ,2nd and 3rd , lift landing and their tie beam of staircase at Overhead Tank (OHT), indicating poor compaction and workmanship. 2. Deviation in Verticality of column alignment has been observed. 3. Reinforcement is exposed at 5th, 6th & 7 th landing of staircase and between the conical wall and bottom ring beam. 4. Minor leakages occurring from Mechanical installations and Bottom dome.
2 8152383 Dhawarra GOV OHT / 008 / DIKWAHA Yes No No Yes No No Yes No No No No No No Resolved 1. Major honeycombing has been observed in 1st ,2nd and 3rd , lift landing and their tie beam of staircase at Overhead Tank (OHT), indicating poor compaction and workmanship. 2. Reinforcement is exposed at 2nd tie beam of staircase and Bottom dome. 3. All DI pipes have been installed without proper clamping/support arrangement also the alignment of DI pipes is not as per the drawings. (Closed Sr. No. 3).
3 8152383 Dhawarra GOV OHT / 027 / CHITTARWARA Yes No No No No No Yes No No No No No No 1. Major honeycombing and exposed steel has been observed in the ring beam, columns and slab of Overhead Tank (OHT). 2. Leakage has been observed from the bottom dome of tank. (Closed) 3. Voids and exposed steel is observed in the junction point of beam and column of OHT. 4. Crack has been observed in the OHT columns.
4 8152383 Dhawarra GOV OHT / 011 / MAHUA BANDH Yes Yes No Yes No No Yes No No No No No No 1. Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2. Misalignment has been observed in the OHT columns. 3. Reinforcement is exposed from the certain parts of OHT. 4. Cracks observed at junction point of column and beam.
5 8152383 Dhawarra GOV OHT / 004 / NAGARA DANG Yes Yes No No No No No No No No No No No 1. Major honeycomb and reinforcement is exposed in Tie beam, ring beam & bottom dome. 2. Deviation in Verticality of column alignment has been observed.
6 8152383 Dhawarra GOV OHT / 030 / SAITHWARA Yes No No No No No Yes No No No No No No Resolved Resolved 1. Major honeycomb and reinforcement are exposed in cylindrical wall, ring beam of bottom dome and top dome. 2. Leakage is observed from the container wall and bottom dome of OHT.
7 8152383 Dhawarra GOV OHT / 005 / BUDHWARA Yes Yes No No No No Yes No No No No No No 1. Major honeycombing and exposed steel has been observed in most of the OHT concrete work including ring beam and bottom dome. 2. Verticality of column alignment is observed which is indicating poor compaction and workmanship. 3. Voids has been observed between the conical wall and ring beam of tank.
8 8152383 Dhawarra GOV OHT / 017 / ARI Yes Yes No No No No Yes No No No No No No Resolved 1. Major honeycombing and reinforcement are exposed from the bottom dome & ring beam of OHT. 2. Misalignment has been observed in the OHT columns. 3. Leakage is observed from cylindrical wall and bottom dome of OHT. (Sr. No. 3 Closed)
9 8152383 Dhawarra GOV OHT / 025 / NARWARA Yes No No No No No Yes No No No No No No Resolved 1. Major honeycombing and exposed steel has been observed in most of the OHT concrete work including OHT columns and bottom dome. 2. Continues leakage and seepage is observed at the bottom dome. (Closed Sr. No. 2)
10 8152383 Dhawarra GOV ESR-01 Yes Yes No No No No Yes No No No No No No 1. Major honeycombing and exposed steel has been observed in balcony near staircase, 5th outer brace and on main ring beam Overhead Tank (OHT). 2. Verticality of column alignment is observed which is indicating poor compaction and workmanship. 3. Cracks has been observed in the junction point of beam and column. 4. Voids has been observed in the conical wall of tank. 5. Leakages spotted has been found in the container wall & bottom dome.
11 8152383 Dhawarra GOV OHT / 019 / SWASA MAF No Yes No No No No Yes No No No No No No Resolved 1. Deviation in verticality of columns indicating poor compaction and workmanship. 2. The Leakage has been observed from OHT container. (Closed Sr. No. 2)
12 8152383 Dhawarra GOV OHT / 018 / KAITHUARA Yes Yes No Yes No No No No No No No No No Major honeycombing & reinforcement is exposed from the OHT slab.
13 8152383 Dhawarra GOV OHT / 010 / DHAWARRA Yes Yes No No No No Yes No No No No No No 1. Major honeycombing and exposed steel has been observed in most of the OHT concrete work including OHT beams and bottom dome. 2. Leakage has been observed in the OHT. 3. Deviation in verticality of columns indicating poor compaction and workmanship.
14 8152383 Dhawarra GOV OHT / 013 / BHANDARA Yes No No No No No No No No No No No No Major honeycombing and exposed steel has been observed in certain parts of Overhead Tank (OHT).
15 8152383 Dhawarra GOV OHT / 022 / PACH PAHARA Yes No No No No No Yes No No No No No No 1.Major Honeycombs has been observed in the certain parts of OHT. 2.Gaps has bene observed at the junction points of beams and column. 3.The tank was found empty during the visit, Live seepage found between junction of RCC tank and Connecting Pipe.
16 8152383 Dhawarra GOV OHT / 009 / BILKHI Yes Yes No Yes No No No No No No No No No 1.Major honeycombing has been observed in 7th flight and 4th tie beam of staircase at Overhead Tank (OHT), indicating poor compaction and workmanship. 2.Reinforcement is exposed at column above 4th brace and 3rd & 4th brace. 3.Misalignment in verticality of Upper Column lifts for Staircase and OHT.
17 8152383 Dhawarra GOV OHT / 014 / ATRAR MAF Yes Yes No Yes No No Yes No No No No No No 1.• Honeycomb and Reinforcement is exposed in OHT ring beam, walkway and stairs. 2• Misalignment has been observed in the columns of OHT. 3• Leakage and Seepage is observed at the bottom dome of the OHT.
18 8152383 Dhawarra GOV OHT / 015 / DIGARIYA Yes Yes No Yes No No No No No No No No No 1• Major honeycombing has been observed in 2nd, 5th ,7th tie beam and Midlanding of staircase at Overhead Tank (OHT), indicating poor compaction and workmanship. 2• Misalignment has been observed in the OHT columns. 3.• Reinforcement is exposed at bottom dome near inlet pipe, balcony near staircase and on main ring beam near inlet pipe.
19 8152383 Dhawarra GOV OHT / 007 / BASORA Yes Yes No Yes No No No No No No No No No 1• Major honeycombing has been observed in 3rd, 4th brace, Main ring beam, significant Exposed steel and honeycomb conical wall and balcony of Overhead Tank (OHT), indicating poor compaction and workmanship, with significant leakages at bottom dome. 2• Misalignment in columns of tanks and staircase has been observed in the OHT. 3• Reinforcement is exposed at 4th tie beam of staircase and 3rd and 4th Landing of staircase bottom dome near inlet pipe, main ring beam.
20 8152383 Dhawarra GOV OHT / 021 / RAHELIA Yes Yes No No No No Yes No No No No No No 1.• Major honeycombing has been observed in 1st, 2nd, 3rd ,4th tie beam of staircase at Overhead Tank (OHT). 2• Deviation in verticality of columns indicating poor compaction and workmanship. 3• Voids has been observed in the junctions points of beam and column of OHT.
21 8152383 Dhawarra GOV OHT / 006 / TOLA SOYAM Yes Yes No No Yes No Yes No No No No No No Resolved 1.• Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2• The diameter of columns in the OHT is not uniform across the OHT. 3• Deviation in verticality of columns indicating poor compaction and workmanship.- Closed Drawing submitted. 4• Concrete quality in the OHT is not proper as per the visual inspection carried out. 5• Voids has been observed in the junctions points of beam and column of OHT.
22 8152383 Dhawarra GOV OHT / 029 / KAR PAHARIYA Yes No No Yes No No Yes No No No No No No 1.Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2• Reinforcement is exposed at staircase landing of Overhead Tank (OHT). 3• Cracks observed where staircase landing. 4• The Leakage has been observed from OHT container.
23 8152383 Dhawarra GOV OHT / 012 / LEVA Yes Yes No No No No Yes No No No No No No 1• Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2• Misalignment has been observed in the OHT columns. 3• Cracks observed at junction point of column and beam. 4• The Leakage has been observed from OHT.
24 8152383 Dhawarra GOV OHT / 016 /MUDHARI Yes Yes No Yes No No No No No No No No No 1• Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2• Misalignment has been observed in the OHT columns. 3• Reinforcement is exposed from the certain parts of OHT.
25 8152383 Dhawarra GOV OHT / 026 / TIKARIYA PANWARI Yes Yes No Yes No No No No No No No No No 1• Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2• Misalignment has been observed in the OHT columns. 3• Reinforcement is exposed from the certain parts of OHT.
26 8152383 Dhawarra GOV OHT / 003 / LUHEDI No No No No No No No No No No No No No