Sno. Scheme Status Pump Status District Name Agency Name Scheme Id Scheme Name Covered Village Regular Water Supply Last Data Receive Date EE E&M Verification Remark
Total 199 100
1 Off Balrampur Larsen & Toubro Ltd 20024850 Achalpur Roop Water Supply Scheme 2 2 16-11-2026 09:30 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 13-11-2026
2 Off Balrampur Larsen & Toubro Ltd 20102006 ACHKAWAPUR WATER SUPPLY SCHEME 1 1 05-10-2026 08:55 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 13-11-2026
3 Off Balrampur Larsen & Toubro Ltd 20024836 Adhinpur Water Supply Scheme 1 0 16-11-2026 09:30 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
4 Off Balrampur Larsen & Toubro Ltd 8361868 AHIRAULI BUJURG 1 1 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
5 Off Balrampur Larsen & Toubro Ltd 20098106 ALLAH NAGAR WATER SUPPLY SCHEME 5 5 16-11-2026 09:10 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
6 Off Balrampur Larsen & Toubro Ltd 20063141 Ambar Nagar Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 13-11-2026
7 Off Balrampur Larsen & Toubro Ltd 20016384 Ararpakar water supply scheme 2 2 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 13-11-2026
8 Off Balrampur Larsen & Toubro Ltd 20069210 BABHNI BUZURG WATER SUPPLY 3 3 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
9 Off Balrampur Larsen & Toubro Ltd 20093954 Baghail Khand Water Supply Scheme 1 0 15-11-2026 03:37 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
10 Off Balrampur Larsen & Toubro Ltd 20063164 Baghani Water Supply Scheme 2 2 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
11 Off Balrampur Larsen & Toubro Ltd 20025434 Baghisheer_Chatur Nagar Water Supply Scheme 3 3 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
12 Off Balrampur Larsen & Toubro Ltd 20102656 BAHUTI WATER SUPPLY SCHEME 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
13 Off Balrampur Larsen & Toubro Ltd 8361251 Baijpur 2 2 05-09-2026 10:09 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 12-11-2026
14 Off Balrampur Larsen & Toubro Ltd 20019505 Bakauli Rajpur water supply scheme 1 1 05-09-2026 10:09 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
15 Off Balrampur Larsen & Toubro Ltd 20021197 Bakhar Kotwa Water Supply Scheme 1 1 24-10-2026 10:15 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
16 Off Balrampur Larsen & Toubro Ltd 20018765 Baksaria water supply scheme 2 0 14-11-2026 03:34 PM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 12-11-2026
17 Balrampur Larsen & Toubro Ltd 20094205 BALBHARIA WATER SUPPLY SCHEME 2 2 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
18 Off Balrampur Larsen & Toubro Ltd 20024851 Balpur Water Supply Scheme 2 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
19 Off Balrampur Larsen & Toubro Ltd 20021236 Bangarh Pipri Water Supply Scheme 1 1 14-11-2026 03:44 PM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
20 Off Balrampur Larsen & Toubro Ltd 20025443 Bankatwa Kalan_Beli Kalan Water Supply Scheme 2 2 16-11-2026 09:31 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
21 Off Balrampur Larsen & Toubro Ltd 20069280 Banse Dila Water Supply 2 2 05-09-2026 10:09 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
22 Off Balrampur Larsen & Toubro Ltd 20091710 Barahya Pakri Water Supply Scheme 2 2 05-09-2026 10:09 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
23 Off Balrampur Larsen & Toubro Ltd 20069316 Baram Bhari Water Supply 2 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
24 Off Balrampur Larsen & Toubro Ltd 20018771 Bardahawa water supply scheme 1 1 16-11-2026 09:30 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
25 Off Balrampur Larsen & Toubro Ltd 20063146 Basawan Bankat Water Supply Scheme 1 0 05-09-2026 10:09 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 13-11-2026
26 Off Balrampur Larsen & Toubro Ltd 20094213 BEERPUR SEMRA WATER SUPPLY SCHEME 1 0 26-09-2026 08:28 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 04-11-2026
27 Off Balrampur Larsen & Toubro Ltd 20018775 Bela water supply scheme 2 2 16-11-2026 09:41 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 12-11-2026
28 Off Balrampur Larsen & Toubro Ltd 20102008 BELHASA WATER SUPPLY SCHEME 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
29 Off Balrampur Larsen & Toubro Ltd 20069289 Belwa Binoohni Water Supply 2 2 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
30 Off Balrampur Larsen & Toubro Ltd 20024697 Bhagata Water Supply Scheme 1 0 16-11-2026 09:30 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
31 Off Balrampur Larsen & Toubro Ltd 20091588 Bhagawatpur &Fattejot Water Supply Sechme 2 0 16-11-2026 09:31 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
32 Off Balrampur Larsen & Toubro Ltd 20098096 BHAGWANPUR RATANPUR WATER SUPPLY SCHEME 1 0 16-11-2026 09:20 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
33 Off Balrampur Larsen & Toubro Ltd 20069284 Bhikhpur Water Supply 1 1 05-09-2026 10:09 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
34 Off Balrampur Larsen & Toubro Ltd 20097259 Bhirawa-Deoriya Inayat Water Supply Scheme 3 0 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
35 Off Balrampur Larsen & Toubro Ltd 20020869 Bhojpur Santari water supply scheme 2 2 16-11-2026 09:30 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
36 Off Balrampur Larsen & Toubro Ltd 20094292 CHAINPUR WATER SUPPLY SCHEME 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 13-11-2026
37 Off Balrampur Larsen & Toubro Ltd 20025423 Cheetarapara-Pidria Bujurg Water Supply Scheme 3 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
38 Off Balrampur Larsen & Toubro Ltd 20093995 CHHITAUNI WATER SUPPLY SCHEME 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
39 Off Balrampur Larsen & Toubro Ltd 20024834 Chichoori Sihania Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
40 Off Balrampur Larsen & Toubro Ltd 20024979 Chiutihva Water Supply Scheme 1 0 05-09-2026 10:09 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
41 Off Balrampur Larsen & Toubro Ltd 20016390 Chulhabhari water supply scheme 1 1 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
42 Off Balrampur Larsen & Toubro Ltd 20018762 Deonagar water supply scheme 1 1 05-09-2026 10:09 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
43 Off Balrampur Larsen & Toubro Ltd 20025901 Dharam nagar water supply scheme 2 2 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
44 Off Balrampur Larsen & Toubro Ltd 20102009 DHAURAHRA WATER SUPPLY SCHEME 1 0 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
45 Off Balrampur Larsen & Toubro Ltd 20021227 Dhauri Kalan Water Supply Scheme 1 1 10-10-2026 03:04 PM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 04-11-2026
46 Off Balrampur Larsen & Toubro Ltd 20091454 DHUSAH WATER SUPLY 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
47 Off Balrampur Larsen & Toubro Ltd 20098713 Dubaulia Water Supply scheme 2 0 16-11-2026 09:10 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
48 Off Balrampur Larsen & Toubro Ltd 20025961 Dulhapur Hanumant Nagar water supply scheme 1 1 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 13-11-2026
49 Off Balrampur Larsen & Toubro Ltd 20021201 Dulhin Dih Water Supply Scheme 1 1 05-09-2026 10:09 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 04-11-2026
50 Balrampur Larsen & Toubro Ltd 20094166 Ganeshpur Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
51 Balrampur Larsen & Toubro Ltd 20092841 GANESHPUR WATER SUPPLY SCHEME 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
52 Off Balrampur Larsen & Toubro Ltd 20092907 Ganveria Bujurg Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
53 Off Balrampur Larsen & Toubro Ltd 20094141 Gaura Bagnaha Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
54 Off Balrampur Larsen & Toubro Ltd 20021246 Ghogra Water Supply Scheme 3 3 16-11-2026 09:30 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
55 Off Balrampur Larsen & Toubro Ltd 20018767 Gobari water supply scheme 2 2 05-09-2026 10:09 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 13-11-2026
56 Off Balrampur Larsen & Toubro Ltd 20024696 Gondawa Water Supply Scheme 1 1 14-11-2026 02:52 PM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
57 Off Balrampur Larsen & Toubro Ltd 20024698 Gopalpur Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
58 Off Balrampur Larsen & Toubro Ltd 20021238 Haraiya Chandrasi Water Supply Scheme 1 0 29-10-2026 08:28 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
59 Off Balrampur Larsen & Toubro Ltd 20092853 Haribansh Pur water supply scheme 1 1 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
60 Balrampur Larsen & Toubro Ltd 20094250 Imlia Khader Water Supply Scheme 2 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
61 Off Balrampur Larsen & Toubro Ltd 20021239 Imlia Koder Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
62 Off Balrampur Larsen & Toubro Ltd 20021232 Imlia Water Supply Scheme 1 1 14-09-2026 04:00 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
63 Off Balrampur Larsen & Toubro Ltd 20024838 Itai Abdullah Water Supply Scheme 1 0 19-10-2026 03:35 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
64 Off Balrampur Larsen & Toubro Ltd 20069313 Jafrabad Water Supply 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
65 Off Balrampur Larsen & Toubro Ltd 20019344 Jamuni Kalan water supply scheme 1 1 05-09-2026 10:09 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
66 Off Balrampur Larsen & Toubro Ltd 20092868 JHAUHANA WATER SUPPLY SCHEME 2 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
67 Off Balrampur Larsen & Toubro Ltd 20098121 JHAWWA WATER SUPPLY SCHEME 2 0 16-11-2026 09:20 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
68 Off Balrampur Larsen & Toubro Ltd 20092942 Jorawarpur Water Scheme 1 0 16-11-2026 09:31 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
69 Off Balrampur Larsen & Toubro Ltd 20094245 Kalyanpur Bargadawa Water Supply Scheme 1 0 16-11-2026 09:41 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
70 Off Balrampur Larsen & Toubro Ltd 20021183 Kandbhari Water Supply Scheme 1 1 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 13-11-2026
71 Off Balrampur Larsen & Toubro Ltd 20069303 Kapauasherpur Water Supply 1 1 10-09-2026 03:57 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
72 Off Balrampur Larsen & Toubro Ltd 20094149 Karmaiti Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
73 Off Balrampur Larsen & Toubro Ltd 20025416 Katia-Madhawajot 2 2 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
74 Off Balrampur Larsen & Toubro Ltd 20069285 Khagaijot Water Supply 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
75 Off Balrampur Larsen & Toubro Ltd 20094216 Khaira water Supply Scheme 1 1 20-10-2026 03:58 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
76 Off Balrampur Larsen & Toubro Ltd 20016033 Kolawa water supply scheme 1 1 22-09-2026 12:13 PM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 12-11-2026
77 Balrampur Larsen & Toubro Ltd 20021242 Kolhai Water Supply Scheme 1 1 16-11-2026 08:59 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
78 Off Balrampur Larsen & Toubro Ltd 20097925 KONHDAURA & NEWAL GANJ WATER SUPPLY 2 0 13-11-2026 03:52 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
79 Off Balrampur Larsen & Toubro Ltd 20018774 Lakshmanpur water supply scheme 1 1 15-09-2026 04:29 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
80 Balrampur Larsen & Toubro Ltd 20018760 Lalnagar Sipahiya water supply scheme 1 1 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
81 Off Balrampur Larsen & Toubro Ltd 20094010 LALPUR BISHUNPUR WATER SUPPLY SCHEME 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
82 Off Balrampur Larsen & Toubro Ltd 20021250 Lokia Tahir Water Supply Scheme 1 0 08-11-2026 12:48 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
83 Off Balrampur Larsen & Toubro Ltd 20016392 Luchuiya water supply scheme 1 1 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
84 Off Balrampur Larsen & Toubro Ltd 20097904 MADARA WATER SUPPLY SCHEME 1 1 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
85 Off Balrampur Larsen & Toubro Ltd 20093959 MADRAHWA WATER SUPPLY SCHEME 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
86 Balrampur Larsen & Toubro Ltd 20094023 Mahadeo Atarpari Water Supply Scheme 2 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
87 Off Balrampur Larsen & Toubro Ltd 20069296 Majhari Tappa Wak 1 0 14-11-2026 03:55 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
88 Off Balrampur Larsen & Toubro Ltd 20018766 Majhgawan water supply scheme 2 2 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
89 Off Balrampur Larsen & Toubro Ltd 20021243 Mardahwa Kalan Water Supply Scheme 2 2 16-11-2026 09:30 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
90 Off Balrampur Larsen & Toubro Ltd 20017720 Mhagaipur water supply scheme 1 0 03-11-2026 06:12 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 03-11-2026
91 Off Balrampur Larsen & Toubro Ltd 20069278 Mirzapur Water Supply 2 2 05-09-2026 10:09 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 13-11-2026
92 Off Balrampur Larsen & Toubro Ltd 20094037 MOTIPUR HARAHWA WATER SUPPLY SCHEME 1 0 08-10-2026 05:51 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
93 Balrampur Larsen & Toubro Ltd 20024827 Motipur Kalan Water Supply Scheme 1 1 16-11-2026 09:30 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
94 Off Balrampur Larsen & Toubro Ltd 20094043 MOTIPUR WATER SUPPLY SCHEME 1 0 27-09-2026 08:48 PM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 12-11-2026
95 Off Balrampur Larsen & Toubro Ltd 20094050 Mudila Water Supply Scheme 1 0 16-11-2026 12:29 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
96 Balrampur Larsen & Toubro Ltd 20024840 Nachaura Water Supply Scheme 1 1 16-11-2026 09:30 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
97 Off Balrampur Larsen & Toubro Ltd 20018759 Nachauri water supply scheme 1 1 05-09-2026 10:09 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 04-11-2026
98 Off Balrampur Larsen & Toubro Ltd 20094089 Nand Nagar Water Supply Scheme 1 0 05-09-2026 10:09 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
99 Balrampur Larsen & Toubro Ltd 20093963 NATHAI DIH WATER SUPPLY SCHEME 1 1 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
100 Off Balrampur Larsen & Toubro Ltd 20092882 NAVA KOLE 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
101 Off Balrampur Larsen & Toubro Ltd 20024835 Orajhar Water Supply Scheme 1 0 24-10-2026 09:23 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
102 Off Balrampur Larsen & Toubro Ltd 20024854 Padari Raikwar Water Supply Scheme 3 0 16-11-2026 09:20 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
103 Off Balrampur Larsen & Toubro Ltd 20069299 Parsapalai Dih Water Supply 1 0 06-11-2026 03:54 PM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
104 Off Balrampur Larsen & Toubro Ltd 20025435 Parsia Gosain -Ahlad Nagar Water Supply Scheme 2 2 17-09-2026 01:47 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
105 Off Balrampur Larsen & Toubro Ltd 20024855 Peher Water Supply Scheme 2 0 16-11-2026 08:49 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
106 Off Balrampur Larsen & Toubro Ltd 20069302 Pipra Yaqaoob Water Supply 1 1 17-09-2026 05:56 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
107 Off Balrampur Larsen & Toubro Ltd 20094211 Pooranpur Arjunpur Water Supply Scheme 1 0 05-09-2026 10:09 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 13-11-2026
108 Off Balrampur Larsen & Toubro Ltd 20018769 Prem Nagar water supply scheme 1 1 05-09-2026 10:09 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
109 Off Balrampur Larsen & Toubro Ltd 20102005 PUREY CHEETAN WATER SUPPLY SCHEME 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
110 Off Balrampur Larsen & Toubro Ltd 20094238 Rajderwa Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
111 Off Balrampur Larsen & Toubro Ltd 20024843 Rajghat Water Supply Scheme 1 1 16-11-2026 09:30 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 13-11-2026
112 Off Balrampur Larsen & Toubro Ltd 20098093 RANIPUR WATER SUPPLY SCHEME 1 0 16-11-2026 08:07 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
113 Off Balrampur Larsen & Toubro Ltd 20069292 Rantan Pur Water Supply 3 0 05-09-2026 10:09 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
114 Off Balrampur Larsen & Toubro Ltd 20094192 Razderwa Tharoo Water Supply Scheme 2 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
115 Off Balrampur Larsen & Toubro Ltd 20018761 Razwapur water supply scheme 1 0 05-09-2026 10:09 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
116 Off Balrampur Larsen & Toubro Ltd 20102004 ROOP NAGAR WATER SUPPLY SCHEME 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
117 Off Balrampur Larsen & Toubro Ltd 20025431 Sahiapur_Amahawa Water Supply Scheme 3 3 16-11-2026 09:20 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
118 Off Balrampur Larsen & Toubro Ltd 20097257 Sahjaura Water Supply 1 0 16-11-2026 09:41 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
119 Off Balrampur Larsen & Toubro Ltd 20021254 Sarai Khas Water Supply Scheme 1 0 16-11-2026 09:30 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
120 Off Balrampur Larsen & Toubro Ltd 20021190 Sathi Water Supply Scheme 2 2 15-11-2026 02:02 PM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
121 Off Balrampur Larsen & Toubro Ltd 20021221 Semri Water Supply Scheme 1 0 16-11-2026 09:20 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 13-11-2026
122 Off Balrampur Larsen & Toubro Ltd 20069282 Shankarpur Water Supply 2 0 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
123 Off Balrampur Larsen & Toubro Ltd 20094203 Shitlapur Water Supply Scheme 1 0 16-11-2026 09:41 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026
124 Off Balrampur Larsen & Toubro Ltd 20069308 Sikaramafi Water Supply 2 2 05-09-2026 10:09 AM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 10-11-2026
125 Off Balrampur Larsen & Toubro Ltd 20093969 SINGH MOHINI WATER SUPPLY SCHEME 1 0 05-11-2026 10:56 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 13-11-2026
126 Off Balrampur Larsen & Toubro Ltd 20092873 SIRIA WATER SUPPLY SCHEME 1 1 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
127 Off Balrampur Larsen & Toubro Ltd 20094234 Sishania Ghoplapur Water Supply Scheme 1 0 15-11-2026 03:26 PM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
128 Off Balrampur Larsen & Toubro Ltd 8360736 Someraha 2 2 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
129 Off Balrampur Larsen & Toubro Ltd 20098092 SOWNAHWA & HARIHARPUR WATER SUPPLY SCHEME 2 0 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
130 Off Balrampur Larsen & Toubro Ltd 20094079 Teganwar Water Supply Scheme 1 0 24-10-2026 09:44 AM All equipment actual data not shown on portal so that automation integration verification is pending.
Update Date : 04-11-2026
131 Off Balrampur Larsen & Toubro Ltd 20092892 Tendua bhanpur Water Supply Scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 06-11-2026
132 Off Balrampur Larsen & Toubro Ltd 20094052 TENDUA NAGAR WATER SUPPLY SCHEME 2 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
133 Balrampur Larsen & Toubro Ltd 20018768 Thakurapur water supply scheme 1 0 16-11-2026 09:41 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 04-11-2026
134 Off Balrampur Larsen & Toubro Ltd 20102001 THUDHWALIYA WATER SUPPLY SCHEME 1 0 16-11-2026 09:20 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
135 Off Balrampur Larsen & Toubro Ltd 20094105 Turkaulia Water Supply Scheme 1 0 13-11-2026 03:10 PM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 12-11-2026
136 Off Balrampur Larsen & Toubro Ltd 20016395 Udaipur water supply scheme 2 2 16-11-2026 09:31 AM 1. Turbidity Analyzer is not working. 2. Online Flowmeter is not calibrated and showing false reading. 3. HLS is showing false reading and needs to be calibrated. 4. Chlorine Analyzer is showing false reading and needs to be calibrated. 5. Pressure Transmitter is showing false reading and needs to be calibrated.
Update Date : 10-11-2026
137 Off Balrampur Larsen & Toubro Ltd 20025440 Uprahula-Barayal Water Supply Scheme 6 6 15-11-2026 03:37 PM All equipment's actual data not shown on portal so that automation integration verification is pending.
Update Date : 06-11-2026